Installation Instructions
Installer Setting - Ceiling Height Selection
This function is to adjust FAN Airflow rate according to ceiling height (for ceiling type product)
Ceiling Height Selection Table
Ceiling Height Level
01
Low
Decrease the indoor airflow rate 1 step from standard level
02
Medium
Set the indoor airflow rate as standard level
03
High
Increase indoor airflow rate 1 step from standard level
04
Very high
Increase indoor airflow rate 2 steps from standard level
•
Ceiling height setting is available only for some products.
•
Ceiling height of 'Very high' function may not exist depending on the indoor unit.
•
Refer to the product manual for more details.
16 New Wide Wired Remote Controller
Pressing and holding the
button
1
for 3 seconds enters the remote
controller setup mode. If it is not held
for 3 seconds, it enters the user setup
mode.
2
If moving to ceiling height selection menu by
pressing
button, it indicates as pictured
below.
3
Select ceiling height value by pressing
button. (01:Low, 02:Medium,
03:High, 04:Very high)
Function Code
Thermistor setting
4
Press
button to save.
Pressing the
button will exit the settings
5
mode. If
is not pressed, the remote
controller will automatically exit setup mode
after 25 seconds with no input. If the set
button is not pressed, the changes will not
take effect.
Description
Installer Setting - Static Pressure Setting
This function is applied to only duct type indoor units. Setting this in other cases will cause malfunction.
Static Pressure Setting Table
Pressure selection
01
V-H
02
F-H
03
V-L
04
F-L
Installation Instructions
Press and hold the
button
1
for 4 seconds to enter the
installer setting mode. The timer
will display 01:01.
If pressing
button repeatedly, it
2
moves to static pressure selection menu
as pictured below.
3
Select static pressure by pressing
button.
(01:V-H, 02:F-H, 03:V-L, 04:F-L)
Function Code
Pressure
Press
button to save.
4
5
Pressing the
button will exit the settings
mode. If
is not pressed, the remote
controller will automatically exit setup mode
after 25 seconds with no input.
If the set button is not pressed, the changes
will not take effect.
Function
Zone state
ESP standard value
Variable
High
Fixed
High
Variable
Low
Fixed
Low
Owner's & Installation Manual 17