Installation instruction
Installer Setting -Ceiling Height Selection
This function is to adjust FAN Airflow rate according to ceiling height (For ceiling type product)
<Ceiling Height Selection Table>
Ceiling Height Level
01
Low
Decrease the indoor airflow rate 1 step from standard level
02
Standard
Set the indoor airflow rate as standard level
03
High
Increase indoor airflow rate 1 step from standard level
04
Very high
Increase indoor airflow rate 2 steps from standard level
•
Ceiling height setting is available only for some products.
•
Ceiling height of ʻVery highʼ function may not exist depending on the indoor unit.
•
Refer to the product manual for more details.
16 New Wide Wired Remote Controller
1
If pressing
button long for 3
seconds, it enters into remote
controller setter setup mode.
- If pressing once shortly, it enters
into user setup mode. Please press
more than 3 seconds for sure.
2
If moving to ceiling height selection menu by
pressing
button, it indicates as picture
below.
3
Select ceiling height value by pressing
button. (01:Low, 02:Standard,
03:High,
Function Code
Thermistor setting
4
Press
button to save.
Pressing
button will exit settings mode.
5
❈ After setup, it automatically gets out of
setup mode if there is no button input for
25 seconds.
❈ When exiting without pressing set button,
the manipulated value is not reflected.
Description
Installer Setting -Static Pressure Setting
This function is applied to only duct type. Setting this in other cases will cause malfunction.
<Static Pressure Setting Table>
Pressure selection
01
V-H
02
F-H
03
V-L
04
F-L
Installation instruction
1
Press
button for 4 seconds
to enter the installer setting
mode until timer segment
displays "01:01".
2
If pressing
button repeatedly, it moves to
static pressure selection menu as picture
below.
3
Select static pressure by pressing
button.
(01:V-H, 02:F-H, 03:V-L, 04:F-L)
Function Code
Pressure
4
Press
button to save.
5
Pressing
button will exit settings mode.
❈ After setup, it automatically gets out of
setup mode if there is no button input for
25 seconds.
❈ When exiting without pressing set button,
the manipulated value is not reflected.
Function
Zone state
ESP standard value
Variable
High
Fixed
High
Variable
Low
Fixed
Low
Ownerʼs & Installation Manual 17