Installer Setting -Ceiling Height Selection; Installer Setting -Static Pressure Setting - LG PQRCVSL0 Owners & Installation Manual

New wide wired remote controller
Hide thumbs Also See for PQRCVSL0:
Table of Contents

Advertisement

Installation instruction

Installer Setting -Ceiling Height Selection

This function is to adjust FAN Airflow rate according to ceiling height (For ceiling type product)
<Ceiling Height Selection Table>
Ceiling Height Level
01
Low
Decrease the indoor airflow rate 1 step from standard level
02
Standard
Set the indoor airflow rate as standard level
03
High
Increase indoor airflow rate 1 step from standard level
04
Very high
Increase indoor airflow rate 2 steps from standard level
Ceiling height setting is available only for some products.
Ceiling height of ʻVery highʼ function may not exist depending on the indoor unit.
Refer to the product manual for more details.
16 New Wide Wired Remote Controller
1
If pressing
button long for 3
seconds, it enters into remote
controller setter setup mode.
- If pressing once shortly, it enters
into user setup mode. Please press
more than 3 seconds for sure.
2
If moving to ceiling height selection menu by
pressing
button, it indicates as picture
below.
3
Select ceiling height value by pressing
button. (01:Low, 02:Standard,
03:High,
Function Code
Thermistor setting
4
Press
button to save.
Pressing
button will exit settings mode.
5
❈ After setup, it automatically gets out of
setup mode if there is no button input for
25 seconds.
❈ When exiting without pressing set button,
the manipulated value is not reflected.
Description

Installer Setting -Static Pressure Setting

This function is applied to only duct type. Setting this in other cases will cause malfunction.
<Static Pressure Setting Table>
Pressure selection
01
V-H
02
F-H
03
V-L
04
F-L
Installation instruction
1
Press
button for 4 seconds
to enter the installer setting
mode until timer segment
displays "01:01".
2
If pressing
button repeatedly, it moves to
static pressure selection menu as picture
below.
3
Select static pressure by pressing
button.
(01:V-H, 02:F-H, 03:V-L, 04:F-L)
Function Code
Pressure
4
Press
button to save.
5
Pressing
button will exit settings mode.
❈ After setup, it automatically gets out of
setup mode if there is no button input for
25 seconds.
❈ When exiting without pressing set button,
the manipulated value is not reflected.
Function
Zone state
ESP standard value
Variable
High
Fixed
High
Variable
Low
Fixed
Low
Ownerʼs & Installation Manual 17