Installation instruction
2) General Ventilation product
No.
Function
Code
1
Test Run
01
01 : Test Run Setup
Address Setting
2
02
00~FF : Address of Central Control
3
SA(Supply Air) ESP
03
<ESP level>
01 : Low
02 : High
4
EA(Exhaust Air) ESP
04
03 : Super High
01 : Normal
5
Product Direction
05
02 : Opposite
01 : Supply Air First
6
Quick Refresh Priority
06
02 : Exhaust Air First
00 : Slave
7
Master Setting
07
01 : Master
00 : Slave
8
Override Setting
08
01 : Master
00 : Auto-Off
9
Dry Contact
09
01 : Auto-On
10
Release Of 3 Minute Delay
10
01 : Set
01 : Variable
11
Zone State
11
02 : Fixed
Humidification for Singular
00 : Not in Use
12
13
Ventilation
01 : Use
Humidification for Heat Mode
00 : Automatic
13
14
Ventilation
01 : Manual
❊
Some contents may not be displayed depending on the product function
10 New Wide Wired Remote Controller
Value
<ESP value>
<Example>
0~255
Function Code
ESP step
ESP value
Installer Setting -Test Run Mode
After installing the product, you must run a Test Run mode.
For details related to this operation, refer to the product manual.
Installation instruction
1
If pressing
button long for 3 seconds,
it enters into remote controller setter
setup mode.
- If pressing once shortly, it enters into
user setup mode. Please press more
than 3 seconds for sure.
- Please cancel the right and left of wind
direction for RAC product.
Function Code
Set
2
Setup figure '01' blinks at the lower part
of indication window.
3
Press
button to start.
4
During the test run, pressing the below
button will exit the test run.
- Select operation, temperature
up/down, wind flow control, wind
direction, start/stop button.
Ownerʼs & Installation Manual 11