Installation Instructions
26 New Wide Wired Remote Controller
Move to Low Ambient Heating Operation
4
setting by pressing
button.
5
Press
button to setup Low
Ambient Heating Operation.
0 : not use
1 : use - compressor off(0℉/ -18℃) / compressor on(5℉ / -15℃)
2 : use - compressor off(5℉ / -15℃) / compressor on(10℉ / -12℃)
3 : use - compressor off(10℉/ -12℃) / compressor on(15℉ / -9℃)
Emergency heater operation in Low Ambient temperature
- compressor off : Emergency heater enabled
- compressor on : Emergency heater disabled
Move FAN Speed Setting during
6
Emergency Heater Operation by pressing
button.
Press
button to setup FAN
7
Speed during Emergency Heater
Operation.
0 : fan off
1 : fan on
8
Press
button to save.
Pressing the
button will exit
9
the settings mode. If
is not
pressed, the remote controller will
automatically exit setup mode after 25
seconds with no input. If the set button is
not pressed, the changes will not take
effect.
Installer Setting - Option Function Setting
Setting feature for indoor unit when Plasma purification / Electric heater / Humidifier / Elevation grill
Ventilation kit / Auxiliary heater is newly installed, or installed unit is removed.
Installation Instructions
1
Pressing and holding the
button for
3 seconds enters the remote
controller setup mode. If it is
not held for 3 seconds, it enters
the user setup mode.
If pressing
button repeatedly, it moves to
2
the selected option function code as pictured
below.
Function
Plasma purification
Electric heater
Humidifier
Elevation grill
Ventilation kit
Auxiliary heater
Select existing condition
3
of each mode by pressing
button.
(00: not installed,
01 : installed)
Function Code
Existing condition
Press
button to save.
4
5
Pressing the
button will exit
the settings mode. If
is not
pressed, the remote controller will
automatically exit setup mode after 25
seconds with no input. If the set button is
not pressed, the changes will not take
effect.
Owner's & Installation Manual 27
Code
20
21
22
23
24
25