Check Point
1. Check the power source.(230V ±15%)
2. Check the fan operation is right.
3. Check the current.
4. Check the install condition.
5. Check the CT Sensor Output signal
(ZHBW056A0 / ZHBW076A0 / ZHBW096A0 - Check output the CT Sensor : DC 2.5±0.2V
ZHBW126A0 / ZHBW146A0 / ZHBW166A0 - Check output pin 2.3 of the CT Sensor : DC 2.5±0.2V
ZHBW128A0 / ZHBW148A0 / ZHBW168A0 - Check input_current of the CT sensor : DC 2.5±0.2V)
▶ZHBW056A0 / ZHBW076A0 / ZHBW096A0
▶ ZHBW126A0 / ZHBW146A0 / ZHBW166A0
Red
<CT Sensing Check Point>
- 88 -
Copyright © 2018 LG Electronics Inc. All rights reserved.
Only training and service purposes.
GND
Vdc
Black