Temperature range setting
• Air cooling set temp.
Determine cooling setting temperature range when air temperature is selected as setting temperature.
Only available when remote air temperature sensor is connected.
• Accessory PQRSTA0 should be installed.
• Also, Remote air sensor connection should be set properly.
• Water cooling set temp
Determine cooling setting temperature range when leaving water temperature is selected as setting temperature.
Water condensation on the floor
• While cooling operation, it is very important to keep leaving water temperature higher than 16 °C. Otherwise,
dew condensation can be occurred on the floor.
• If floor is in humid environment, do not set leaving water temperature below 18 °C.
Water condensation on the radiator
• While cooling operation, cold water may not flow to the radiator. If cold water enters to the radiator, dew gener-
ation on the surface of the radiator can be occurred.
• Air heating set temp.
Determine heating setting temperature range when air temperature is selected as setting temperature.
CAUTION
Only available when remote air temperature sensor is connected.
• Accessory PQRSTA0 should be installed.
• Also, Remote air sensor connection should be set properly.
• Water heating set temp
Determine heating setting temperature range when leaving water temperature is selected as setting temperature.
• DHW set temp.
Determine heating setting temperature range of water tank leaving water.
Only available when DHW tank feature is installed.
• DHW tank and DHW tank kit should be installed.
• DIP switch No. 2 and 3 should be set properly.
• Screed drying mode
After installing water pipes for under floor heating, user can select screed drying mode for curing the cement.
- 47 -