Display
Title
code
High temperature
61
in Cond. Pipe
WARNING
Before checking PCB(Inverter) or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby
state of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
Recheck power and
installation condition
Cause of error
• Overload operation
(Outdoor fan constraint,
screened, blocked)
• Unit heat exchanger cont-
aminated
• EEV connector displaced
/ poor EEV assembly
• Poor Cond. Pipe sensor
assembly / burned
- 107 -
Check point & Normal condition
• Check outdoor fan constraint / screened / flow
structure
• Check if refrigerant overcharged
• Check the status of EEV assembly
• Check the status of sensor assembly / burn
CN- C/PIPE
(Violet 3Pin Connector)
Copyright © 2018 LG Electronics Inc. All rights reserved.
Only training and service purposes.