hit counter script

Connection Of Piping - LG AMNH076LQL0 Service Manual

Multi type
Hide thumbs Also See for AMNH076LQL0:
Table of Contents

Advertisement

Connection of Piping

• When connecting indoor units, make sure to connect refrigerant pipes and connection wires to the appropriate con-
nection ports maked with matching alphabets. (A, B, C, D)
:
NOTICE
• Be sure to mark all the local refrigerant piping(liquid
pipes, gas pipes, etc.) for each indoor unit designating
clearly which room it belongs in.(A, B, C, D)
:
NOTICE
For flaring work the piping, follow the instructions in the installation manual to each unit.
Connecting the pipings to the indoor unit
and drain hose to drain pipe
1. Align the center of the pipings and sufficiently tighten
the flare nut by hand.
2. Tighten the flare nut with a wrench.
Outside diameter
mm
inch
Ø6.35
1/4
Ø9.52
3/8
Ø12.7
1/2
Ø15.88
5/8
Ø19.05
3/4
Wrap the insulation material around the
connecting portion.
1. Overlap the connection pipe insulation material and
the indoor unit pipe insulation material. Bind them
together with vinyl tape so that there is no gap.
2. Wrap the area which accommodates the rear piping
housing section with vinyl tape.
Close up a socket for unoccupied room
with a brass cap.
1. Align the center of the piping and sufficiently tighten
the brass cap by hand.
2. Tighten the brass cap with a wrench.
3. Wrap the joint part with insulation.
CAUTIONS
• Never use the plastic cap for sealing.
• Make sure to use brass cap with the end of
pipe sealed or welded tightly.
Torque
kg . m
1.8
4.2
5.5
6.6
6.6
A
B
C
BD Unit Socket
Flare nut
Open-end wrench (fixed)
Flare nut
Wrench
BD Unit Socket
BD Unit
Vinyl tape (wide)
Wrap with vinyl tape
Connecting cable
Vinyl tape(narrow)
BD Unit Socket
Brass cap
Service Manual 85
Installation
D
Pipes
Connection pipe
Indoor unit pipe
Pipe
Pipe sealed
or welded

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Uploaded: cache9/manual/833374/Lg-Amnh076lql0.html%3Fpage%3D85.gz