hit counter script

LG AS-W1863 Series Svc Manual page 72

Universal air conditioner
Table of Contents

Advertisement

Troubleshooting Guide
When the horizontal louver does not operate.
Trouble 5
• Confirm that the vertical louver is normally geared with the shaft of Stepping Motor.
• If the regular torque is detected when rotating the vertical louver with hands ⇒ Normal
• Check the connecting condition of CN-U/D Connector
• Check the soldering condition(on PCB) of CN-U/D Connector
• Confirm that there is DC +12V between pin ➀ of CN-U/D and GND.
• Confirm that there is a soldering short at following terminals.
- Between
41
- Between
4
- Between
10
• Confirm the assembly condition that are catching and interfering parts in the link of the
vertical louver
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Check the operating circuit of the vertical louver
,
,
and
of MICOM
42
43
44
,
and
of IC01M
5 , 6
7
,
and
of IC01M
11 , 12
13
If there are no problems after above checks.
- 72 -
LGE Internal Use Only

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

As-w2463 series

Table of Contents

Uploaded: cache9/manual/1037961/Lg-As-W1863-Series.html%3Fpage%3D72.gz