Outdoor
1. Remove the control cover from the unit by loosening
the screw.
Connect the wires to the terminals on the control
board individually.
2. Secure the cable onto the control board with the cord
clamp.
3. Refix the control cover to the original position with the
screw.
4. Use a recognized circuit breaker 20A(12k) between
the power source and the unit.
A disconnecting device to adequately disconnect all
supply lines must be fitted.
Circuit
Breaker
18k
(A)
20
CAUTION: According to the confirmation of the above conditions, prepare the
wiring as follows.
1. Never fail to have an individual power circuit specifically for the air conditioner. As for the method of
wiring, be guided by the circuit diagram posted on the inside of control cover.
2. The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from
vibrations to which the unit is subjected during the course of transportation. Check them and make
sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3. Specification of power source.
4. Confirm that electrical capacity is sufficient.
5. See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on
the name plate.
6. Confirm that the cable thickness is as specified in the power source specification.
(Particularly note the relation between cable length and thickness.
7. Always install an earth leakage circuit breaker in a wet or moist area.
8. The following would be caused by voltage drop.
• Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal function
of the overload.
9. The means for disconnection from a power supply shall be incorporated in the fixed wiring and have
an air gap contact separation of at least 3mm in each active(phase) conductors.
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Grade
24k
30
Outdoor Unit
Connecting cable
Connecting cable
- 23 -
Installation
Terminal block
Over 5mm
Cover control
LGE Internal Use Only