Protection from total current control
I CT1 control
• If the operating current reaches I1, the operating frequency of the compressor decrease.
• After decreasing the operating frequency by 1step, if operating current is below I1 for 60 seconds continuous-
ly, the operating frequency of compressor increase by 1step.
I CT2 control
• If the operating current of the appliance reaches I2, the compressor stop instantly and 2 minutes later the
compressor restart again.
• If CT2 occurs 5 times within 1hour, the appliance turn off and display ERROR CODE 7.
Control table
Model
1
AS-W1863_ Series
2
AS-W2463_ Series
cf. I1 is set the lowest level between intial value and in case dectection of dc paeak current.
Protection from DC Peak Current
I DC Peak Current Error by a fault signal of IPM
• If the operating current of IPM reaches 35A ±3A, the compressor stop instantly.
• If DC PEAK occurs 5 times within 1 hour, the appliance turns off and display ERROR CODE 6.
I DC Peak Current Error by the compressor lock
• If the DC LINK voltage below DC 140V occurs 5 times within 1 hour while the compressor is operating, the
appliance turns off and display ERROR CODE 6.
I DC Peak Current Error by the Outdoor Fan Lock
• If it's 5 times within 1 hour in case of the temperature of outdoor pipe TH is over 65°C while the compressor is
operating, the appliance turns off and display ERROR CODE 6.
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
❇ I1:Current of operating frequency down
I2: Current of compressor cut off
Outdoor temp ≥ 38°C
Cooling
Heating
10.5
11.5
13.5
14.0
- 43 -
I1
Outdoor temp < 38°C
Cooling
Heating
11
14
14.5
Operation
I2
12
14.0
15.5
LGE Internal Use Only