Product doesn't operate with the remote controller.
Trouble 2
While the compressor has been stopped, the compressor does not operate
When the compressor stopped Indoor Fan is driven by a low speed.
At this point the wind speed is not controlled by the remote controller.
(When operated in the Sleeping Mode, the wind speed is set to the low speed as force).)
Caused by the remote controller.
When the mark (
screen, replace battery.
When the detect switch (double key) inside the
remote controller door is fault, it is impossible to
operate temperature regulating(
speed selecting.
Check the connecting circuit between the
remote controller MICOM(No.30)-R17(2Ω)-IR-
LED-Tr-R16(2.2kΩ)
Turn on main power.
owing to the delaying function for 2 minutes after stopped.
) is displayed in LCD
/
) and wind
Caused by other parts except
the remote controller
Check the contact of CN-DISP 1, 2 connector
Check DISP PWB Ass'y
-Voltage between CN1
Check point
• Check the connecting circuit between
MICOM PIN
• Check receiver ass'y
-53-
-
: DC +5V