Soap water method
(1) Remove the caps from the 2-way and 3-way valves.
(2) Remove the service-port cap from the 3-way valve.
(3) To open the 2-way valve turn the valve stem counter-
clockwise approximately 90°, wait for about 2~3 sec,
and close it.
(4) Apply a soap water or a liquid neutral detergent on
the indoor unit connection or outdoor unit connec-
tions by a soft brush to check for leakage of the con-
necting points of the piping.
(5) If bubbles come out, the pipes have leakage.
3. Evacuation
Connect the charge hose end described in the pre-
ceding steps to the vacuum pump to evacuate the
tubing and indoor unit.
Confirm the "Lo" knob of the manifold valve is open.
Then, run the vacuum pump.
The operation time for evacuation varies with tubing
length and capacity of the pump.
The following table shows the time required for evac-
uation.
Required time for evacuation
when 30 gal/h vacuum pump is used
If tubing length is less than
10m (33 ft)
10 min. or more
When the desired vacuum is reached, close the "Lo"
knob of the manifold valve and stop the vacuum
pump.
4. Finishing the job
With a service valve wrench, turn the valve stem of
liquid side valve counter-clockwise to fully open the
valve.
Turn the valve stem of gas side valve counter-clock-
wise to fully open the valve.
Loosen the charge hose connected to the gas side
service port slightly to release the pressure, then
remove the hose.
Replace the flare nut and its bonnet on the gas side
service port and fasten the flare nut securely with an
adjustable wrench. This process is very important to
prevent leakage from the system.
Replace the valve caps at both gas and liquid side
service valves and fasten them tight.
This completes air purging with a vacuum pump.
The air conditioner is now ready to test run.
If tubing length is longer
than 10m (33 ft)
15 min. or more
3-way valve
(Close)
2-way valve
(Open)
Manifold valve
Pressure
gauge
Open
Vacuum pump
-36-
Gas side
Liquid side
Hexagonal wrench
Indoor unit
Outdoor unit
Lo
Hi
Close
Cap