Balance Refrigerant of the 3-way Valve
(Gas leakage)
Indoor unit
• Procedure
(1) Confirm that both the 2-way and 3-way valves
are set to the back seat.
(2) Connect the charge set to the 3-way valve's
port.
– Leave the valve on the charge set closed.
– Connect the charge hose to the service port.
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Liquid side
Gas side
Lo
OPEN
CLOSE
3-Way
valve
Open
3-Way
valve
Open
(3) Open the valve (Lo side) on the charge set and
discharge the refrigerant until the gauge indi-
cates 0 kg/cm
– If there is no air in the refrigerant cycle (the
pressure when the air conditioner is not running
is higher than 1 kg/cm
erant until the gauge indicates 0.5 to 1
kg/cm
2
G. if this is the case, it will not be neces-
sary to apply a evacuatin.
– Discharge the refrigerant gradually; if it is dis-
charged too suddenly, the refrigeration oil will
also be discharged.
- 49 -
Troubleshooting Guide
Outdoor unit
2
G.
G), discharge the refrig-
2
LGE Internal Use Only