Connecting the cable between indoor unit and outdoor unit
Connect the cable to the Indoor unit.
Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually
according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No.
are the same as those of the indoor unit.)
• The above circuit diagram is subject to change without notice.
• The earth wire should be longer than the common wires.
• When installing, refer to the circuit diagram behind the panel front of the indoor unit.
• Connect the wires firmly so that they may not be pulled out easily.
• Connect the wires according to color codes, referring to the wiring diagram.
If a power plug is not used, provide a circuit
breaker between power source and the unit as
shown by.
The power cord connected to the "A" unit should be selected according to the following specifications(Type "B"
approved by HAR or SAA).
NORMAL CROSS
7k
-SECTIONAL AREA
0.75
Unit(A)
Indoor
Cable Type(B)
H05VV-F
The power connecting cable connecting the indoor and outdoor unit should be selected according to the following
specifications (Type "B" approved by HAR or SAA).
NORMAL CROSS
7k
-SECTIONAL AREA
0.75
Cable Type(B) H07RN-F
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Connecting the cable between indoor unit and outdoor unit
(mm
2
Grade
9k~14k
18k
24k
1.0
1.5
2.5
Indoor
Indoor
Indoor
H05VV-F
H05VV-F
H05VV-F
(mm
2
)
Grade
9k~14k
18k
24k
1.0
1.5
2.5
H07RN-F
H07RN-F
H07RN-F
Main power source
Air
Conditioner
)
- 19 -
Circuit Breaker
Use a circuit
breaker or time
delay fuse.