hit counter script

Operation - LG AS-W096ERH0 Svc Manual

Universal air conditioner
Hide thumbs Also See for AS-W096ERH0:
Table of Contents

Advertisement

Operation

Operation
Function of Controls
• DISPLAY
1) C/O Model
Operation Indicator
• ON while in appliance operation, OFF while in appliance pause.
• Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Timer Indicator
• ON while in timer mode (on/off), OFF when timer mode is completed or canceled.
Comp. Running Incidator
• While in appliance operation, ON while in outdoor unit compressor running, OFF while in compressor off.
2) H/P Model
Operation Indicator
• ON while in appliance operation, OFF while in appliance pause.
• Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Timer Indicator
• ON while in timer mode (on/off), OFF when timer mode is completed or canceled.
Defrost Indicator
• OFF except when hot start during heating mode operation or while in defrost control.
Protection of the evaporator pipe from frosting
• If the indoor pipe temperaure is below 0°C in 7 min. after the compressor operates without pause while in
cooling cycle operation mode,
➔ compressor, outdoor fan are turned off.
• When indoor pipe temp. is 7°C or higher after 2 min pause of compressor
➔ compressor, outdoor fan is turned on according to the condition of the room temperature.
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Comp. free
6˚C
Comp. Step 4
3˚C
Comp. Step 2
0˚C
Comp. off
Indoor pipe
temp.
- 28 -
7˚C
LGE Internal Use Only

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Uploaded: cache9/manual/792165/Lg-As-W096erh0.html%3Fpage%3D28.gz