EQUIPMENT SELECTION PROCEDURE

Correction Factors
Cooling / Heating Correction Factors
For Single Zone Mega, Standard Efficiency, and Mega 115V Wall Mounted systems, calculate the equivalent length of the liquid line from the
outdoor unit to the indoor unit. Also, determine the elevation difference of the indoor unit above or below the outdoor unit. Find corresponding
cooling or heating capacity correction factors as shown below. Multiply the correction factors by the cooling or heating capacity obtained from
the capacity tables using design conditions. The resultant is the NET cooling or heating capacity.
Cooling and Heating Capacity Coefficient
Table 46: Mega, Standard Efficiency Cooling and Heating Capacity Coefficient Factors.
LS090HEV2,
LS120HEV2,
LS090HFV3,
Rate of
LS120HFV3
Capacity
LS180HEV2,
Change (%)
LS240HEV2,
LS180HFV3,
LS240HFV3
Table 47: Mega 115V Cooling and Heating Capacity Coefficient Factors.
Rate of
LS090HXV2
Capacity
LS120HXV2
Change (%)
Equivalent Piping Length for Piping Components
Table 48: Equivalent Piping Length for Elbows.
Component
1/4
3/8
Elbow (ft.)
0.5
0.6
Altitude Correction Factor
The impact of air density must be considered on systems installed at a significant altitude above sea level, therefore, locally accepted
altitude correction factors using ASHRAE guidelines must be applied.
72 | PERFORMANCE DATA
Factors�
Operation
Mode
16.4
24.6
Cooling
100
100
Heating
100
100
Cooling
100
100
Heating
100
100
Operation
Mode
16.4
24.6
Cooling
100
100
Heating
100
100
1/2
5/8
3/4
0.7
0.8
1.2
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG " is a registered trademark of LG Corp.
Piping Length (ft.)
32.8
49.2
65.6
82.0
97.7
93.0
-
-
98.3
95.0
-
-
99.0
97.0
95.0
-
99.2
97.6
96.0
-
Piping Length (ft.)
32.8
49.2
65.6
82.0
97.7
93.0
-
-
98.3
95.0
-
-
Size (Inches)
7/8
1
1-1/8
1-1/4
1.3
1.5
1.6
1.8
98.4
114.8
131.2
147.6
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
98.4
114.8
131.2
147.6
-
-
-
-
-
-
-
-
1-3/8
1-1/2
1-5/8
1-3/4
2.0
2.1
2.3
2.5
164.0
-
-
-
-
164.0
-
-
2-1/8
2.8