Always follow local codes when selecting and installing copper pipe and piping system components. Approved piping for use with LG Single Zone products will be marked “R410 RATED” along the length of the pipe. Piping wall thickness must meet local code requirements and be approved for a maximum operating pressure of 551 psi. When bending piping, try to keep the number of bends to a minimum, and use the largest radii possible to reduce the equivalent length of installed piping;...
Failure to do so will cause significant performance degradation. Proper leak checks must be performed. Using isolation valves does not automatically void any LG product warranty, however, a limited warranty will be voided in whole or part if any field supplied accessory fail in any way that causes product failure.
Page 30
Pipe Sleeves at Penetrations LG requires that all pipe penetrations through walls, floors, and pipes buried underground be properly insulated and routed through an appropriate wall sleeve of sufficient size to prevent compression of refrigerant pipe insulation and free movement of the pipe within the sleeve.
FLARING AND BRAZING PROCEDURES Flaring and Brazing Procedures One of the main causes of refrigerant leaks is a defective connection. For LG HVAC systems, the installer needs to know how perform both flared and brazed connections successfully. • During installation, it is imperative to keep the piping system free of contaminants and debris such as copper burrs, slag, or carbon dust.
Refer to the table below and on the next two pages for error codes that are generated from the indoor and outdoor units. These codes are the most common. Your particular system might generate additional codes not listed here. Please contact LG Support if you see these types of errors and a simple power cycle has not corrected the issue.
No cables were spliced and no wire caps are present. LG-supplied cable was used between the indoor unit and its zone controller. No cables were spliced and no wire caps are present. Appropriate crimping tool was used to attach ring or spade terminals at all power wiring and control cable terminations.
Page 69
ISO 9001: 2008 LG ELECTRONICS INC. For further technical materials such as submittals, engineering manuals, service manuals, and catalogs, visit www.lghvac.com. LG Customer Information Center, Commercial Products 1-888-865-3026 USA Follow the prompts for commercial A/C products. IM_SZ_HighEfficiency_WallMounted_09_23 LG Electronics, U.S.A., Inc.