Electrical Data for Mega, Standard Efficiency Models
Table 5: 208-230V, 60Hz, 1-Phase Single Zone Mega, Standard Efficiency System Electrical Data Table.
Nominal
Unit Model
Hertz Voltage
Tons
No.
3/4
LS090HEV2
1
LS120HEV2
1-1/2
LS180HEV2
2
LS240HEV2
60
208 - 230
3/4
LS090HFV3
1
LS120HFV3
1-1/2
LS180HFV3
2
LS240HFV3
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Electrical Data for Mega 115V Models
Table 6: 115V, 60Hz, 1-Phase Single Zone Mega 115V System Electrical Data Table.
Nominal
Unit Model
Hertz Voltage
Tons
No.
3/4
LS090HXV2
60
1
LS120HXV2
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Mega, Standard Efficiency, and Mega 115V Outdoor Units
Voltage Range
(Min. to Max.) MCA
10.0
10.0
15.0
15.0
187-253
10.0
10.0
15.0
15.0
Voltage Range
MCA
(Min. to Max.)
15
115
98-132
15
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG " is a registered trademark of LG Corp.

ELECTRICAL DATA

Compressor Motor
Compressor
RLA
MOP
Quantity
Cooling
15
1
7.0
15
1
7.0
20
1
10.0
20
1
10.0
15
1
7.0
15
1
7.0
20
1
10.0
20
1
10.0
Maximum Overcurrent Protection (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
RLA = Rated Load Amps.
FLA = Full Load Amps.
Compressor Motor
Compressor
RLA
MOP
Quantity
Cooling
25
1
11.0
25
1
11.0
Maximum Overcurrent Protection (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
RLA = Rated Load Amps.
FLA = Full Load Amps.
Outdoor Fan Motor Indoor Fan Motor
Heating
W
FLA
7.0
43
0.4
7.0
43
0.4
10.0
85
0.4
10.0
85
0.4
7.0
43
0.4
7.0
43
0.4
10.0
85
0.4
10.0
85
0.4
Outdoor Fan Motor Indoor Fan Motor
Heating
W
FLA
11.0
43
0.4
11.0
43
0.4
PRODUCT DATA | 13
W
FLA
30
0.4
30
0.4
58
0.4
58
0.4
30
0.4
30
0.4
58
0.4
58
0.4
W
FLA
30
0.4
30
0.4