PERFORMANCE DATA
Cooling Capacity
Cooling Capacity Table for LS090HXV2 (LSU090HXV2 + LSN090HXV2)
Table 24: LSN090HXV2 / LSU090HXV2 Cooling Capacities.
Outdoor
Air
64 / 53
Temp.
(°F DB)
TC SHC PI
TC SHC
4
5.51
4.90 0.31 6.89
23
5.92
5.26 0.31 7.12
25
6.01
5.34 0.32 7.18
30
6.24
5.55 0.34 7.35
35
6.47
5.75 0.36 7.52
40
6.70
5.96 0.39 7.69
45
6.94
6.17 0.41 7.85
50
7.17
6.37 0.43 8.02
55
7.40
6.58 0.46 8.19
60
7.63
6.79 0.48 8.36
65
7.56
6.72 0.50 8.25
70
7.49
6.66 0.53 8.14
75
7.43
6.60 0.55 8.04
80
7.36
6.54 0.58 7.93
85
7.29
6.48 0.60 7.82
90
7.22
6.42 0.62 7.72
95
7.15
6.36 0.65 7.61
100
6.96
6.19 0.66 7.43
105
6.77
6.02 0.67 7.26
110
6.59
5.85 0.68 7.08
115
6.35
5.65 0.69 6.83
118
6.21
5.52 0.69 6.68
122
6.02
5.63 0.70 6.48
DB: Dry Bulb Temperature (°F)
WB: Wet Bulb Temperature (°F)
SHC: Sensible Capacity (kBtu/h)
PI: Power Input (kW) (includes compressor, indoor fan motor and
outdoor fan motor)
1. All capacities are net, evaporator fan motor heat is deducted.
2. Grey shading indicates reference data. When operating at this temperature, these values can be
different if the system is not running consistently..
60 | PERFORMANCE DATA
Indoor Air Temperature (°F DB / °F WB)
68 / 57
72 / 61
PI
TC
SHC
PI
5.21
0.37
8.27
5.53
0.43
5.60
0.37
8.32
5.94
0.44
5.67
0.38
8.36
6.00
0.44
5.85
0.40
8.46
6.16
0.46
6.03
0.42
8.56
6.31
0.47
6.22
0.43
8.67
6.47
0.48
6.40
0.45
8.77
6.63
0.50
6.58
0.47
8.88
6.78
0.51
6.76
0.49
8.98
6.94
0.52
6.94
0.51
9.08
7.10
0.54
6.91
0.53
8.94
7.10
0.56
6.88
0.55
8.79
7.11
0.58
6.86
0.58
8.65
7.11
0.60
6.83
0.60
8.51
7.12
0.63
6.80
0.62
8.36
7.12
0.65
6.77
0.65
8.22
7.13
0.67
6.74
0.67
8.07
7.13
0.69
6.60
0.68
7.91
7.00
0.70
6.45
0.69
7.75
6.87
0.71
6.30
0.70
7.58
6.74
0.72
6.08
0.71
7.32
6.51
0.73
5.94
0.71
7.16
6.37
0.73
6.06
0.72
6.94
6.49
0.74
TC: Total Capacity (kBtu/h)
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG " is a registered trademark of LG Corp.
77 / 64
80 / 67
TC SHC PI
TC SHC
9.99
5.93 0.50 11.03 6.17 0.54
9.82
6.36 0.52 10.72 6.62 0.57
9.83
6.41 0.52 10.71 6.66 0.57
9.85
6.54 0.53 10.68 6.77 0.57
9.87
6.66 0.54 10.66 6.87 0.58 10.05 7.69
9.90
6.79 0.54 10.63 6.98 0.58 10.31 7.88
9.92
6.92 0.55 10.61 7.09 0.59 10.57 8.07
9.94
7.04 0.56 10.58 7.19 0.59 10.83 8.27
9.96
7.17 0.57 10.56 7.30 0.59 11.09 8.46
9.99
7.29 0.58 10.53 7.41 0.60 11.35 8.66
9.80
7.34 0.60 10.31 7.48 0.62 11.13 8.66
9.61
7.39 0.62 10.09 7.55 0.64 10.91 8.67
9.42
7.43 0.64 9.87 7.62 0.66 10.69 8.67
9.22
7.48 0.66 9.66 7.70 0.67 10.48 8.68
9.03
7.53 0.68 9.44 7.77 0.69 10.26 8.68
8.84
7.57 0.70 9.22 7.84 0.71 10.04 8.69
8.65
7.62 0.72 9.00 7.91 0.73
8.50
7.51 0.73 8.86 7.82 0.74
8.35
7.40 0.74 8.72 7.72 0.75
8.21
7.29 0.75 8.58 7.63 0.77
7.92
7.05 0.76 8.28 7.37 0.77
7.75
6.90 0.76 8.10 7.21 0.78
7.51
7.03 0.77 7.86 7.36 0.79
3. Direct interpolation is permissible.
Capacity as rated: 0 ft. above sea level with 24.6 ft. of refrigerant piping. 0 ft. level difference between
outdoor and indoor units.
Cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet
bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
86 / 72
PI
TC SHC
PI
TC
9.20
6.72
0.44
7.99
9.43
7.22
0.45
8.57
9.54
7.30
0.46
8.75
9.80
7.49
0.48
9.20
0.49
9.65
0.51
10.10 8.48 0.47
0.53
10.55 8.73 0.50
0.55
11.00 8.98 0.52
0.57
11.45 9.23 0.55
0.59
11.90 9.49 0.58
0.61
11.68 9.45 0.61
0.64
11.46 9.41 0.64
0.66
11.24 9.37 0.67
0.69
11.02 9.33 0.70
0.71
10.80 9.29 0.73
0.74
10.58 9.25 0.76
9.82
8.69
0.76
10.36 9.21 0.79
9.65
8.55
0.78
10.17 9.04 0.80
9.48
8.41
0.79
9.99
9.31
8.28
0.80
9.80
8.99
8.00
0.81
9.47
8.80
7.83
0.81
9.27
8.54
7.99
0.82
8.99
Do not extrapolate.
90 / 75
SHC PI
7.10 0.37
7.62 0.37
7.72 0.39
7.97 0.41
8.23 0.44
8.88 0.81
8.71 0.82
8.42 0.83
8.24 0.84
8.40 0.84