ELECTRICAL CONNECTIONS
Figure 26: PZCWRC1 LG Wired Remote Extension Cable.
Verify the connectors are properly inserted.
FAN
SPEED
TEMP
OPER
MODE
Figure 27: Wired Controller Connection on the Indoor Unit
Terminal Block (Appearances and Terminal Placement
Will Vary Depending on Model).
Indoor Unit Terminal Block
GND
3
1(L1)
2
Wired Controller Placement
Wired controllers include a sensor to detect room temperature. To
maintain comfort levels in the conditioned space, the wired control-
ler must be installed in a location away from direct sunlight, high
humidity, and where it could be directly exposed to cold air. Control-
ler must be installed four (4) to five (5) feet above the floor where its
LED display can be read easily, in an area with good air circulation,
and where it can detect an average room temperature.
Do not install the wired controller near or in:
• Drafts or dead spots behind doors and in corners.
• Hot or cold air from ducts.
• Radiant heat from the sun or appliances.
• Concealed pipes and chimneys.
• An area where temperatures are uncontrolled, such as an outside
wall.
Assigning the Thermistor for Temperature Detection
Each indoor unit includes a return air thermistor assigned to sense the temperature. If a wired controller is installed, there is a choice of
sensing temperature with either the indoor unit return air thermistor or the thermistor in the wired controller. It is also an option to set both
thermistors to sense temperature so that indoor unit bases its operation on the first thermistor to reach the designated temperature differen-
tial.
36 | PRODUCT DATA
C/BOX Cable (Plug type)
Extension cable
When using field-supplied controller cable, make sure to connect the yellow to yellow
(communications wire), red to red (12V power wire), and black to black (ground wire)
terminals from the remote controller to the indoor unit terminal blocks.
Terminal Block
CN-REMO CN-CC
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG " is a registered trademark of LG Corp.
To Indoor Unit
CN-REMO
Terminal
Outdoor Unit
3
(L2)
GND
Figure 25: Proper Location for the Wired Controller.
TEMP
roller
Rem
ot e
Cont
NO
YES
TEMP
Remote Controlle r
NO
TEMP
Remote Controlle r
NO
4 to 5 feet
above the floor