hit counter script

LG LS090HFV3 Engineering Manual page 11

Single zone mega, standard efficiency, and mega 115v wall mounted
Hide thumbs Also See for LS090HFV3:
Table of Contents

Advertisement

Table 3: Single Zone Standard Efficiency System Specifications.
System Model Number (IDU/ODU)
Cooling Capacity (Min/Rated/Max) (Btu/h)
Cooling Power Input
(kW)
1
Heating Capacity (Min/Rated/Max) (Btu/h)
Heating Power Input
(kW)
1
COP
Max. Heating Capacity (Btu/h)
Outdoor 17°F (WB)/Indoor 70°F (DB)
EER
SEER
HSPF
Power Supply (V/Hz/Ø)
Outdoor Unit Operating Range
Cooling (°F DB)
Heating (°F WB)
Indoor Unit Operating Range
Cooling (°F WB)
Heating (°F DB)
Indoor Temperature Setting Range
Cooling (°F)
Heating (°F)
Unit Data
Refrigerant Type
2
Refrigerant Control
IDU Sound Pressure
dB(A) (H/M/L/Sleep)
3
ODU Sound Pressure
dB(A)
3
Unit Weight (lbs)
IDU (Net / Shipping)
ODU (Net / Shipping)
Power/Communication Cable
4
Compressor
Compressor Type (Qty)
Fan
Indoor Unit Type (Qty)
Outdoor Unit Type (Qty)
Motor/Drive
Airflow Rate
Indoor Unit Max/H/M/L (CFM)
Outdoor Unit (Max. [CFM])
Piping
Liquid Line (in, OD)
Vapor Line (in, OD)
Condensation Line (OD, ID)
Additional Refrigerant Charge (oz/ft)
Pipe Length
(Minimum/Maximum)(ft)
5
Piping Length
(no add'l refrigerant, ft)
5
Max Elevation Difference (ft)
EEV: Electronic Expansion Valve
IDU: Indoor Unit
This unit comes with a dry helium charge.
This data is rated 0 ft above sea level with 24.6 of refrigerant line per indoor unit and a 0 ft level
difference outdoor and indoor units.
Cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet
bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 59ºF wet
bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
LS090HFV3
(LSN090HFV3 /
LSU090HFV3)
3,070 ~ 9,000 ~10,330
0.82
3,070 ~ 10,900 ~ 12,520 3,070 ~ 12,000 ~ 13,780 3,685 ~ 19,000 ~ 22,997 3,685 ~ 22,000 ~25,260
0.95
11.47
8,760 (80%)
10.98
17
9.0
42 / 36 / 28 / 21
50
19.2 / 25.4
55.3 / 60
(No. x AWG)
459 / 353 / 264 / 148
953
1/4
3/8
27/32, 5/8
0.22
9.8 / 49.2
24.6
23
ODU: Outdoor Unit
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG " is a registered trademark of LG Corp.
GENERAL DATA
LS120HFV3
LS180HFV3
(LSN120HFV3 /
(LSN180HFV3 /
LSU120HFV3)
LSU180HFV3)
3,070 ~ 12,000 ~ 13,780 3,685 ~ 18,000 ~ 18,493 3,685 ~ 22,000 ~ 24,000
1.25
1.05
11.43
9,640 (80%)
15,270 (80%)
9.60
17
9.0
208-230/60/1
14 to 118
14 to 65
53 to 75
60 to 86
64 to 86
60 to 86
R410A
EEV
42 / 36 / 28 / 21
48 / 43 / 38 / 32
50
19.2 / 25.4
55.3 / 60
4 x 14
Twin Rotary (1)
Cross Flow (1)
Propeller (1)
Brushless Digital Controlled/Direct
459 / 353 / 264 / 148
689 / 512 / 459 / 371
953
1/4
3/8
27/32, 5/8
0.22
9.8 / 49.2
24.6
23
Power Input is rated at high speed.
1
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A
2
refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
3
All communication / connection (power) cable from the outdoor unit to the indoor unit is field supplied
4
and must be a minimum of four-conductor, 14 AWG, stranded, shielded or unshielded (if shielded, it
must be grounded to the chassis of the outdoor unit only), and must comply with applicable local and
national codes. For detailed electrical information, please see the Electrical Data section.
Piping lengths are equivalent.
5
Specifications
LS240HFV3
(LSN240HFV3 /
LSU240HFV3)
1.65
2.2
1.74
2.02
10.92
10.86
17,680 (80%)
10.91
10.00
17
17
9.0
9.0
48 / 43 / 38 / 32
55
55
26 / 30
26 / 30
98.1 / 108
98.1 / 108
689 / 512 / 459 / 371
1,730
1,730
1/4
1/4
1/2
1/2
27/32, 5/8
27/32, 5/8
0.26
0.26
9.8 / 65.6
9.8 / 65.6
24.6
24.6
32.8
32.8
PRODUCT DATA | 11

Advertisement

Table of Contents
loading

Table of Contents