Installation
Selection of the best location
Indoor unit
Install the air conditioner in the location that satis-
fies the following conditions.
• The place shall easily bear a load exceeding four
times the indoor unitʼs weight.
• Sufficient space should be available to inspect
the unit as in the figure shown on the right.
• The place where the unit is installed shall be lev-
eled.
• The place shall be suitable for easy connection of
the indoor unit with the outdoor unit.
• The place where the unit is installed should not
be affected by electrical noise.
• The place where air circulation in the room will be
good .
• There should not be any heat source or steam
near the unit
Service space
Select an installation site where the following con-
ditions are satisfied and that meets your cus-
tomer's approval.
• Where the floor is strong enough to bear the
indoor unit weight.
• Where the floor is not significantly inclined.
• Where nothing blocks the air passage.
• Where condensate can be properly drained.
• Where sufficient clearance for installation and
maintenance can be ensured.
• Where there is no possibility of flammable gas
leakage.
• Where optimum air distribution can be ensured.
• Where piping between indoor and outdoor units
is possible within the allowable limit (Refer to the
installation manual of the outdoor unit.)
• Keep the indoor and outdoor unit, power cable
and transmission wiring, at least 1m from TVs
and radios, to prevent distorted pictures and stat-
ic.(Depending on the type and source of the elec-
trical waves, static may be heard even when
more than 1 m away.)
Type
CEU Type
CFU Type
(Unit: mm)
A
B
788
1080
1066
1358
Front side
100 or
100 or
more
more
1000 or
150 or
more
more
[IMPORTANT]
Leave sufficient clearance for air
inlet and maintenance.
Installation Manual 7
Installation
Window
Air flow
direction
175 or
more
Air inlet
direction
Base
Window