Installation

How to connect wirings

Remove the electric parts Box cover and connect the wiring
Fasten with
accessory clamp

Wiring Connection

Connect the wires to the terminals on the control board individually according to the outdoor unit con-
nection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of
indoor unit respectively.
Terminal Block Indoor
1(L)
2(N)
INDOOR POWER INPUT
WARNING : Make sure that the screws of the terminal are free from looseness.
CAUTION : The Power cord connected to the unit should be selected according
to the following specifications.
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power circuit specifically for the air conditioner. As for the
method of wiring, be guided by the circuit diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come
loose from vibrations to which the unit is subjected during the course of transportation.
Check them and make sure that they are all tightly fastened. (If they are loose, it could
cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage
marked on the name plate.
6) Confirm that the cable thickness is as specified in the power source specification.
(Particularly note the relation between cable length and thickness.)
7) In a wet or moist area, always install an earth leakage circuit breaker.
8) The following would be caused by voltage drop.
• Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of
the normal function of the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and
have an air gap contact separation of at least 3mm in each active(phase) conductors.
12
Indoor Unit
Power Supply wiring
ground wiring
Transmission wiring
(Field wiring)
(Field wiring)
Outdoor unit Indoor unit
SODU SODU
3
4
Fasten with clamp
Power supply wiring
ground wiring
Transmission wiring
Central controller
IDU IDU
INTERNET
DRY1 DRY2 GND
Outdoor unit
12V