hit counter script

LG LS090HEV1 Engineering Manual page 63

Single zone mega wall mounted
Hide thumbs Also See for LS090HEV1:
Table of Contents

Advertisement

Installation of Refrigerant Piping / Brazing Practices
Keep the piping system free of contaminants and debris such as copper burrs, slag, or carbon dust during installation.
All joints are brazed in the field. Single Zone Mega refrigeration system com-
ponents contain very small capillary tubes, small orifices, electronic expansion
valves, oil separators, and heat exchangers that can easily become blocked.
Proper system operation depends on the installer using best practices and utmost
care while assembling the piping system (see Figure 45).
• While brazing, use a dry nitrogen purge operating at a minimum pressure of three
(3) psig and maintain a steady flow.
• Blow clean all pipe sections with dry nitrogen prior to assembly.
• Use a tubing cutter, do not use a saw to cut pipe. De-burr and clean all cuts
before assembly.
• Store pipe stock in a dry place. Keep pipe capped and clean.
• Use adapters to assemble different sizes of pipe.
• Do not use flux, soft solder, or anti-oxidant agents.
• Use a 15% silver phosphorous copper brazing alloy to avoid overheating and produce good flow.
• Protect isolation valves, electronic expansion valves, and other heat-sensitive control components from excessive heat with a wet rag or a
heat barrier spray product
Refrigerant Piping System Insulation
All refrigerant piping, field-provided isolation ball valves, service valves, and elbows shall be completely insulated using closed cell pipe
insulation. The liquid and vapor lines must be insulated separately.
To prevent heat loss/heat gain through the refrigerant piping, all refrigerant piping including liquid lines, and vapor lines shall be insulated
separately. Insulation shall be a minimum 1/2" thick, and thickness needs to be increased based on ambient conditions and local codes.
All insulation joints are to be glued with no air gaps. Insulation material must fit snugly against the refrigeration pipe with no air space
between it and the pipe. Insulation passing through pipe hangers, inside conduit, and/or sleeves must not be compressed. Protect insulation
inside hangers and supports with a second layer. All pipe insulation exposed to the sun and outdoor elements shall be properly protected
with PVC, aluminum vapor barrier, or alternatively placed in a weather-resistant enclosure such as a pipe rack with a top cover; and meet
local codes.
The design engineer performs calculations to determine if the factory-supplied insulation jackets are sufficient to meet local codes and avoid
sweating. Add additional insulation if necessary. Mark all pipes at the point where the insulation jacket ends. Remove the jacket. Install
field provided insulation on the run-out and main trunk pipes first. Peel the adhesive glue protector slip from the insulation jacket and install
the clam-shell jacket over the fitting.
Charging
Each outdoor unit is factory charged (nameplate charge) for the
evaporator as well as a standard 24.6 ft line. Any time a line set is
used longer then the standard 24.6 ft line set length, the refrigerant
charge has to be adjusted.
You must adjust the charge based on how many feet of piping are
added based on 0.22 or 0.33 oz of R410A per foot. The factory
charge accommodates pipe lengths up to the standard length without
requiring refrigerant removal.
Table 19: Charging Capacity.
Capacity
(Btu/h)/Model
Vapor
9k, 12k/HEV1
3/8
9k, 12k/HXV
3/8
18k/HEV1
1/2
24k/HEV1
5/8
INSTALLATION & LAYOUT BEST PRACTICES
Pipe Size
Standard
Length (ft)
Liquid
1/4
24.6
1/4
24.6
1/4
24.6
1/4
24.6
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG " is a registered trademark of LG Corp.
Refrigerant Piping System Layout
Figure 45: Refrigerant Pipe Brazing.
Refrigerant
Piping
If you are uncertain of the unit charge, reclaim, evacuate and weigh in
the correct charge using the unit nameplate (capacity) charge adjusting
for line sets longer than 24.6 ft. This will prevent any interruptions to the
functioning of the unit and possible damage.
Example: A 30 ft line set is used --
5.4 additional feet x 0.33 oz per ft = Add 1.78 oz
of R410A
Max.
Max.
Elevation (ft)
Length (ft)
22.9
49.2
22.9
49.2
32.8
65.6
32.8
65.6
Pressure-reducing
Pipe to
be brazed
Nitrogen
Valve
Taping
Min.
Additional
Length (ft)
Refrigerant (oz/ft)
9.8
0.22
6.6
0.22
9.8
0.33
9.8
0.33
REFRIGERANT DESIGN | 63
Valve

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ls120hev1Ls180hev1Ls240hev1Ls090hxvLs120hxv

Table of Contents

Uploaded: cache9/manual/980974/Lg-Ls090hev1.html%3Fpage%3D63.gz