hit counter script

Electrical Data - LG LS090HEV1 Engineering Manual

Single zone mega wall mounted
Hide thumbs Also See for LS090HEV1:
Table of Contents

Advertisement

Table 4: 208-230V, 60Hz, 1-Phase Single-Zone Mega Inverter System Electrical Data Table.
Model Number Nominal Tons
LS090HEV1
3/4
LS120HEV1
1
LS180HEV1
1-1/2
LS240HEV1
2
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Table 5: 115V, 60Hz, 1-Phase Single Zone Single-Zone Mega 115V System Electrical Data Table.
Model Number Nominal Tons
LS090HXV
3/4
LS120HXV
1
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Compressor
Compressor(A)
Qty
Cool/Heat
1
7.0/7.0
1
7.0/7.0
1
8.81/8.61
1
10.72/10.28
Compressor
Compressor(A)
Qty
Cool/Heat
1
10/10
1
10/10
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG " is a registered trademark of LG Corp.

ELECTRICAL DATA

Mega Inverter and Mega 115V Outdoor Units
Fan Qty
ODU Fan (A)
IDU Fan (A)
1
0.5
1
0.5
1
0.4
1
0.4
Maximum Overcurrent Protection (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
Fan Qty
ODU Fan(A)
IDU Fan (A)
1
0.4
1
0.4
Maximum Overcurrent Protection (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
MCA(A)
MOP(A)
0.5
10
0.5
10
0.4
12
0.4
15
MCA(A)
MOP(A)
0.5
13.5
0.5
13.5
PRODUCT DATA | 13
15
15
20
20
20
20

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ls120hev1Ls180hev1Ls240hev1Ls090hxvLs120hxv

Table of Contents

Uploaded: cache9/manual/980974/Lg-Ls090hev1.html%3Fpage%3D13.gz