Table 2: Single Zone Mega Inverter System Specifications.
System Model Number (IDU/ODU)
Cooling Capacity (Min/Rated/Max) (Btu/h)
Cooling Power Input
(kW)
1
Heating Capacity (Min/Rated/Max) (Btu/h)
Heating Power Input
(kW)
1
COP
Max. Heating Capacity (Btu/h)
Outdoor 17°F (WB)/Indoor 70°F (DB)
EER
SEER
HSPF
Power Supply (V/Hz/Ø)
Outdoor Unit Operating Range
Cooling (°F DB)
Heating (°F WB)
Indoor Unit Operating Range
Cooling (°F WB)
Heating (°F DB)
Indoor Temperature Setting Range
Cooling (°F)
Heating (°F)
Unit Data
Refrigerant Type
2
Refrigerant Control
IDU Sound Pressure
dB(A) (H/M/L/Sleep)
3
ODU Sound Pressure
dB(A)
3
Unit Weight (lbs)
IDU (Net/Shipping)
ODU (Net/Shipping)
Power/Communication Cable
4
Compressor
Compressor Type (Qty)
Fan
IDU Type (Qty)
ODU Type (Qty)
Motor/Drive
Airflow Rate
IDU Max/H/M/L (CFM)
ODU Max (CFM)
Piping
Liquid Line (in, OD)
Vapor Line (in, OD)
Condensation Line (OD, ID)
Additional Refrigerant Charge (oz/ft)
Pipe Length
(Minimum/Maximum)(ft)
5
Piping Length
(no add'l refrigerant, ft)
5
Max Elevation Difference (ft)
EEV: Electronic Expansion Valve
IDU: Indoor Unit
Power Input is rated at high speed.
1
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy
2
R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608
of CAA.
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
3
All power wiring/communication cables are field supplied and are to be minimum 18 AWG, 4-conductor,
4
stranded, shielded and must comply with applicable local and national codes.
Piping lengths are equivalent.
5
LS090HEV1
(LSN090HEV1/
LSU090HEV1)
3,070 ~ 8,500 ~ 9,500
0.68
3,070 ~ 9,000 ~ 10,500
0.78
11.54
5,570 (62%)
12.5
19.0
9.0
39/33/25/19
47
17/20
62/67
(No. x AWG)
Single Rotary (1)
318/276/226/177
953
1/4
3/8
27/32, 5/8
0.22
9.8/49.2
24.6
22.9
ODU: Outdoor Unit
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG " is a registered trademark of LG Corp.
Mega Inverter Specifications
LS120HEV1
LS180HEV1
(LSN120HEV1/
(LSN180HEV1/
LSU120HEV1)
LSU180HEV1)
3,070 ~ 12,000 ~ 13,780 3,685 ~ 17,000 ~ 18,493 3,685 ~ 22,000 ~ 24,000
1.14
3,070 ~ 12,000 ~ 13,780 3,685 ~ 19,000 ~ 22,997 3,685 ~ 22,000 ~ 24,226
0.98
12.24
7,620 (63%)
15,580 (82%)
10.52
17.0
9.2
208-230/60/1
14 to 118
14 to 65
53 to 75
60 to 86
64 to 86
60 to 86
R410A
EEV
39/33/25/19
47
23/28
62/67
4 x 18
Single Rotary (1)
Twin Rotary (1)
Cross Flow (1)
Propeller (1)
Brushless Digital Controlled/Direct
424/353/272/212
629/512/441/353
953
1/4
3/8
27/32, 5/8
0.22
9.8/49.2
24.6
22.9
This unit comes with a dry helium charge.
This data is rated 0 ft above sea level with 24.6 of refrigerant line per indoor unit and a 0 ft level
difference outdoor and indoor units.
Cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet
bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 59ºF wet
bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
GENERAL DATA
LS240HEV1
(LSN240HEV1/
LSU240HEV1)
1.55
2.045
1.59
1.935
11.95
11.37
18,040 (82%)
10.97
10.76
18.0
17.0
9.0
9.0
42/40/35/29
45/40/35/29
51
53
28/30
28/32
78/82
95/104
Twin Rotary (1)
689/600/494/388
1,342
1,766
1/4
1/4
1/2
5/8
27/32, 5/8
27/32, 5/8
0.33
0.33
9.8/65.6
9.8/65.6
24.6
24.6
32.8
32.8
PRODUCT DATA | 11