hit counter script

Piping Materials And Handling - LG MULTI F Installation Manual

Multi-zone heat pump systems
Hide thumbs Also See for MULTI F:
Table of Contents

Advertisement

GENERAL INSTALLATION GUIDELINES

Piping Materials and Handling

Loosening the Flare Nuts
Always use two (2) wrenches to loosen the flare nuts.
Brazing Practices
Keep the piping system free of contaminants and debris such as copper burrs, slag, or carbon
dust during installation. Contaminants can result in mechanical failure of the system.
All joints are brazed in the field. Multi F / Multi F MAX refrigeration system components contain very small capillary tubes, small orifices,
electronic expansion valves, oil separators, and heat exchangers that can easily become blocked. Proper system operation depends on the
installer using best practices and utmost care while assembling the piping system.
• While brazing, use a dry nitrogen purge operating at a minimum pressure of three (3) psig and maintain a steady flow.
• Blow clean all pipe sections with dry nitrogen prior to assembly.
• Use a tubing cutter. De-burr and clean all cuts before assembly.
• Use adapters to assemble different sizes of pipe. Use a 15% silver phosphorous copper brazing alloy to avoid overheating and produce
good flow.
• Protect isolation valves, electronic expansion valves, and other heat-sensitive control components from excessive heat with a wet rag or a
heat barrier spray product.
Do not use flux, soft solder, or anti-oxidant agents.
Do not use a saw to cut pipe.
Piping Materials and Handling
Pipes used for the refrigerant piping system must include the specified thickness, and the
interior must be clean.
Do not bend or damage the pipes while handling and storing, and take care not to con-
taminate the interior with dust, moisture, etc. See Table 11 for care of piping.
Table 11: Three Principles of Refrigerant Piping
Principles
No moisture should be inside the piping.
- Significant hydrolysis of refrigerant oil.
Problems
Caused
- Refrigerant oil degradation.
- Poor insulation of the compressor.
- System does not operate properly.
- EEVs, capillary tubes are clogged.
Solutions - Remove moisture from the piping.
- Piping ends should remain capped until
connections are complete.
-
Do not install piping on a rainy day.
- Connect piping properly at the unit's side.
- Remove caps only after the piping is
cut, the burrs are removed, and after
passing the piping through the walls.
- Evacuate system to a minimum of 500
microns and insure the vacuum holds at
that level for 24 hours
26
Dry
No dust should be inside the piping.
Moisture
- Refrigerant oil degradation.
- Poor insulation of the compressor.
- System does not operate properly.
- EEVs and capillary tubes become
clogged.
- Remove dust from the piping.
- Piping ends should remain capped until
connections are complete.
- Connect piping properly at the side of
the unit.
- Remove caps only after the piping is cut
and burrs are removed.
- Retain the cap on the piping when
passing it through walls, etc.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Figure 20: Refrigerant Pipe Brazing.
Refrigerant
Piping
Figure 19:
Clean
Dust
- Refrigerant gas leaks / shortages.
- Refrigerant oil degradation.
- Poor insulation of the compressor.
- System does not operate properly.
- Test system for air tightness.
- Perform brazing procedures that comply
with all applicable standards.
- Perform flaring procedures that comply
with all applicable standards.
- Perform flanging procedures that
comply with all applicable standards.
- Ensure that refrigerant lines are pressure
tested to 550 psig.
F
MULTI
F
MULTI
MAX
Pressure-reducing
Pipe to
Valve
be brazed
Nitrogen
Valve
Taping
Airtight
No leaks should occur.
Leaks

Hide quick links: