Function
PCB Display(18/24k Model Only)
It is useful to check the cycle data without LGMV.
Operating Method
Whenever you push the Tact Switch, the cycle information will be shown as below.
h After 1page is displayed, subsequently 2page is displayed.
Tact S/W
18/24k
1 time
2 time
3 time
4 time
5 time
6 time
7 time
8 time
9 time
10 time
WARNING : When you push the Tact Switch, use the material non-conduct-
52 Multi Air Conditioner
Item
Low Pressure
Hi Pressure
Discharge Temp.
Cond Out Temp.
Suction Temp.
ODU Air Temp.
Current
Voltage
Comp Hz
DC Link Voltage
TACT-SW1
ing electricity.
Example
890kpa
2900kpa
85°C
-10°C
-10°C
-10°C
15A
230V
100Hz
230V
Display
1page
ʻLPʼ
ʻHPʼ
ʻDSʼ
ʻCSʼ
ʻSSʼ
ʻASʼ
ʻAʼ
ʻVʼ
ʻFʼ
ʻdcʼ
2page
ʼ 89ʼ
ʻ290ʼ
ʼ 85ʼ
ʻ-10ʼ
ʻ-10ʼ
ʻ-10ʼ
ʻ 15ʼ
ʻ230ʼ
ʻ100ʼ
ʻ230ʼ