3. ACP operation by using the LG ACCS
3
Setting the power control (text)
Desired power
Desired operation ratio
Operation switching period
3-48
ACP
The setup item to set the wattage in kW or % is
displayed at the right side of the peak operation ratio
control screen.
If it exceeds the setting value, the air conditioner
operates with the peak operation function periodically
according to the peak power operation rule.
It sets the desired wattage in kW per hour to operate the peak
operation function. It can be adjusted to the half of the
maximum usage by 1kW.
When the value is set by kW, the desired operation ratio(%) is
also changed according to the setting value.
It sets the desired wattage in percentage to operate the peak
operation function. It can be set within the range of 0~100% of
the maximum wattage, which can be controlled by 1%.
When the value is set by %, the desired power (kW) is
changed according to the setting value.
It sets the peak operation period. It can be set within the range
of 5~15 minutes, which can be controlled by 1 minute.