Chapter 6. BUFFER MEMORY AND I/O SIGNAL CONFIGURATON
( 3 )
Out Value (Address 4)
0004
ⓐ Only bits 0, 1, 2, 8, 9 and 10 are usable. If other bit is used, the input signal P(N)6 turns On and
the ERR LED flickers with 0.5 sec cycle.
Bit 0 On : If current count value < set value, OUT1 will be turned On. (output enable)
Bit 1 On : If current count value = set value, OUT1 will be turned On. (output enable)
Bit 2 On : If current count value > set value, OUT1 will be turned On. (output enable)
Bit 8 On : If current count value < set value, OUT2 will be turned On. (output enable)
Bit 9 On : If current count value = set value, OUT2 will be turned On. (output enable)
Bit 10 On : If current count value > set value, OUT2 will be turned On. (output enable)
Bits 0, 1 and 2 can be used in combination.
[Example]
Bits 1 and 2 On : If current count value ≥ set value, OUT1 will be turned On. (output enable)
Bits 0 and 1 On : If current count value ≤ set value, OUT1 will be turned On. (output enable)
Bits 0 and 2 On : If current count value ≠ set value, OUT1 will be turned On. (output enable)
If bits 8, 9 and 10 are used in combination as shown above, the results same as above will be
output to the OUT2.
ⓒ In relation to the channel 1, the address is 0014.
( 4 )
Current Count Value (Addresses 5 and 6)
0005
0006
O :Usable
O :Usable
X :Unusable
6 - 10
X :Unusable
Lower
Upper