hit counter script

Plumbing Materials And Storage Methods - LG AMNW Series Installation Manual

Table of Contents

Advertisement

Plumbing materials and storage methods

Pipe must be able to obtain the specified thickness and should be used with low impurities.
Also when handling storage, pipe must be careful to prevent a fracture, deformity and wound.
Should not be mixed with contaminations such as dust, moisture.
Refrigerant piping on three principles
Drying
Should be no moisture
inside
Items
- Significant hydrolysis of
refrigerant oil
- Degradation of refrigerant
Cause
oil
failure
- Poor insulation of the
compressor
- Do not cold and warm
- Clogging of EEV, Capillary
- No moisture in the pipe
- Until the connection is
completed, the plumbing
pipe entrance should be
strictly controlled.
- Stop plumbing at rainy
day.
Counterm
- Pipe entrance should be
easure
taken side or bottom.
- When removal burr after
cutting pipe, pipe entrance
should be taken down.
- Pipe entrance should be
fitted cap when pass
through the walls.
Cleanliness
No dust inside.
Moisture
- Degradation of refrigerant
oil
- Poor insulation of the
compressor
- Do not cold and warm
- Clogging of EEV, Capillary
- No dust in the pipe.
- Until the connection is
completed, the plumbing
pipe entrance should be
strictly controlled.
- Pipe entrance should be
taken side or bottom.
- When removal burr after
cutting pipe, pipe entrance
should be taken down.
- Pipe entrance should be
fitted cap when pass
through the walls.
INSTALLATION
Airtight
There is no refrigerant
leakage
Dust
- Gas shortages
- Degradation of refrigerant
oil
- Poor insulation of the
compressor
- Do not cold and warm
- Airtightness test should
be.
- Brazing operations to
comply with standards.
- Flare to comply with
standards.
- Flange connections to
comply with standards.
17
Leakage

Advertisement

Table of Contents
loading

Table of Contents

Uploaded: cache9/manual/1696863/Lg-Amnw-Series.html%3Fpage%3D17.gz