hit counter script
Table of Contents

Advertisement

Operation
Portection from overheating of power module
• If the temperature of the heat sink TH. reaches over Toff, the Compressor stop instantly.
• It will be limited the compressor operating frequency according to the heat sink TH.(refer to below FIG.)
• It will be blink 4 times, when the thermistor is open or short, also the temperature is over Toff.
∆T = (T off - T on)
T1 = T on + ∆T
T2 = T on + 2 * ∆T
T off °C
T2 °C
T1 °C
T on °C
COMP
Free
Fc-1
Freq.
Portection from overheating of compressor
• If the temperature of the discharge pipe of compressor reaches over 130°C or below -30°C the compressor
stop instantly.
• It will be limited the compressor operating frequency according to the compressor dome TH.(Refer to below
Fig.)
• Temperature range by COMP SPEC varies by 10°C.
COMP Freq.
Fh min
42 Room Air Conditioner
Fc-2
Fc-1
Fc-2
D-Pipe Temp.
Free
Fc-1
Fc-2
OFF
Heat Sink Temp.
No.
1
2
3
4
OFF
Free
∆T = (T off - T2)/2
No.
T1 = T2 + 2 * ∆T
T3 = T2 + ∆T
1
2
3
4
Fc-2
Fc-1
Free
MODEL
T on
AS-W096QGG1
85
AS-W126RGH1
85
AS-W186TGH1
85
AS-W246TGH1
85
MODEL
T on
AS-W096QGG1
102
AS-W126RGH1
105
AS-W186TGH1
98
AS-W246TGH1
98
T off
95
95
95
95
T off
110
115
108
108

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

As-w126rgh1As-w246tlg1As-w186tgh1As-w246tgh1

Table of Contents

Uploaded: cache9/manual/1245064/Lg-As-W096qgg1.html%3Fpage%3D42.gz