Heating mode operation
• Operating frequency of compressor depend on the difference of the temperature
(= compressor off temp. - intake air temp.)
• Compressor off temp. = setting temp.+3.0°C
on temp. = setting temp.
• If compressor operates at some operation frequency, the operating frequency of compressor cannot be
changed within 30 seconds.
• Condition of compressor turned off
- When intake air temperature reaches +3°C above the setting temperature.
• Condition of indoor fan turned off
- While in compressor on:indoor pipe temp. < 30°C
• While in defrost control, between the indoor and outdoor fans are turned off.
• Compressor 2minutes delay
- After compressor off, the compressor can restart minimum 2 minutes later.
Temp. differences
over 3.0°C
2.5~3.0°C
2.0~2.49°C
1.5~1.99°C
1.0~1.49°C
0.5~0.99°C
0.0~0.49°C
Model
AS-W096QGG1
AS-W126RGH1
AS-W186TGH1
AS-W246TGH1/TLG1
[ The operating freq. step of comp]
[The targeting operating freq. of comp. each model]
Step 1
35
35
25
35
Comp. Operating frequency
Step 7
Step 6
Step 5
Step 4
Step 3
Step 2
Step 1
Comp. Operating frequency
Step 2
Step 3
Step 4 Step 5(Fc)
43
53
64
43
53
64
38
47
65
42
53
61
Operation
Step 6
Step 7
74
77
80
76
78
80
82
87
92
67
70
73
Service Manual 35