FU1-15: Hold Time
FU1?
Hold Time
15
1000 ms
Factory Default:
1000 ms
To set the time to maintain holding torque at zero speed
and stop the operation in a shortest time during
Vector_SPD mode operation
l The inverter runs to maintain speed 0 for the hold
time in Vector_SPD mode and decelerates to stop
after the hold time elapse.
Output Speed
[Hz or Rpm]
Output
Voltage
[V]
à Operation method during Hold Time:
FU1-7 [Stop mode] Decel: zero speed control
FU1-7 [Stop mode] DC-brake
FU1-16: Pre-excitation Current
FU1? Flux Force
16
100.0 %
Factory Default:
100.0 %
FU1-16 [Pre-excitation Current] is applied during FU1-14.
When the motor magnetic flux increases to match the
rated magnetic flux, pre-excitation current starts to
decrease. When the motor magnetic flux reaches to the
rated magnetic flux, the pre-excitation current matches
the rated pre-excitation current.
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
15
1000
1000
Hold time
16
1 00.0
100.0
Chapter 6 - Parameter Description [FU1]
Code
LCD display
FU1-16
Flux Force
Motor magnetic flux
Exciting current
FX-CM
Related Functions:
FU2-34 [No Load Motor Current (RMS)]
FU1-14 [Pre-excitation Time]
FU1-20: Maximum Frequency
FU1-21: Base Frequency
FU1-22: Starting Frequency
FU1?
Max freq
20
60.00 Hz
Factory Default:
60.00 Hz
FU1?
Base freq
21
60.00 Hz
Factory Default:
60.00 Hz
FU1? Start freq
22
0.50 Hz
Factory Default:
0.50 Hz
FU1-20 [Maximum Frequency] is the maximum output
frequency of the inverter. Make sure this maximum
frequency does not exceed the rated speed of the motor.
FU1-21 [Base Frequency] is the frequency where the
inverter outputs its rated voltage. In case of using a
50Hz motor, set this to 50Hz.
FU1-22 [Starting Frequency] is the frequency where the
inverter starts to output its voltage.
91
Factory setting
Setting range
100 [%]
100 ~ 500 [%]
20
60.00
60.00
21
60.00
60.00
22
0.50
0.50