Chapter 5 Power Supply / CPU
5.3.3 Scan Time
The processing time from a 0 step to the 0 step of next scan is called scan time.
1) Expression for scan time
Scan time is the sum of the processing time of scan program that the user has written, of the task program processing time
and the PLC internal processing time.
(1) Scan time = Scan program processing time + Interrupt program processing time + PLC internal processing time
• Scan program processing time = The processing time used to process a user program that is not specified
• Interrupt program processing time = Total of the processing times of interrupt programs executed during
• PLC internal processing time = Self-diagnosis time + I/O refresh time + Internal data processing time
(2) Scan time differs in accordance with the execution or non-execution of interrupt programs and communications
processing, etc.
2) Flags
Scan time is stored in the following system flag area.
• F50 : Maximum scan time (unit: 1 ms)
• F51
Minimum scan time (unit: 1 ms)
:
• F52 : Current scan time (unit: 1 ms)
5.3.4 Scan Watchdog Timer
1)
Watchdog timer is used to detect a delay which is attributable to abnormal operation of sequence program
(Watchdog time is set in menu of basic parameter of KGLWIN.)
2)
When watchdog timer detects an exceeding of preset watchdog time, the operation of PLC is stopped immediately
and all output is off.
3)
If an exceeding of preset watchdog time is expected in sequence program, use 'WDT' instruction.
'WDT' instruction make elapsed watchdog time as zero.
4) In order to clear watchdog error, restarting the PLC or mode change to STOP mode are available.
REMARK
-. Setting range of watchdog : 10 ~ 6,000ms(unit : 10ms)
to a task program.
one scan.
+ Communications service processing time