Chapter 6 - Parameter Description [DRV]
Code
Keypad Display
I/O-01
V1 filter
I/O-02
V1 volt x1
I/O-03
V1 freq y1
I/O-04
V1 volt x2
I/O-05
V1 freq y2
è Important: Increase I/O-01-[Filter Time Constant for
V1 Signal Input] if the V1 signal is affected by noise
causing unstable operation. Increasing this value makes
response time slower.
Set freq
.
I/O-05
I/O-03
I/O-02
V1 Maximum V
V1 Minimum V
I/O-06~10 [Analog Current Input " I " Signal adjustment]
l Command Freq/Torque setting via " I" input terminal
when set DRV-04 [Frequency/Torque mode] to 3 (I)
or 4 (V1+I)
Code
Default setting
I/O-06
10 [msec]
I/O-07
4 [mA]
I/O-08
0 [Hz]
I/O-09
20 [mA]
I/O-10
60 [Hz]
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
Parameter Name
Filter Time Constant for V1
Signal Input
V1 Input
Minimum Voltage
Frequency Corresponding to
V1 Input Minimum Voltage
V1 Input Maximum Voltage
Frequency Corresponding to V1
Input Maximum Voltage
V1 analog input (0~10V)
I/O-04
Setting range
0 ~ 10000 [msec]
0 ~ 20 [mA]
0 ~ Max. freq
0 ~ 20 [mA]
0 ~ Max. freq
Code
Keypad display
I/O-06
I filter
I/O-07
I curr x1
I/O-08
I freq y1
I/O-09
I curr x2
I/O-10
I freq y2
è Important: Increase I/O-06-[Filter time constant for I
signal Input] if the I signal is affected by noise causing
unstable operation. Increasing this value makes
response time slower.
Set freq
I/O-10
I/O-08
I/O-07
I Minimum
current
Related Functions:
DRV-04 [Frequency or Torque Mode]
DRV-16 [Speed Unit Selection]
FU1-20 [Maximum Frequency]
FU2-39 [Control Mode Selection]
I/O-1~10 [Analog Frequency
Command/Torque]
DRV-01: Acceleration Time
DRV? Acc. time
01
20.0 sec
Factory Default:
20.0 sec
80
Parameter Name
Filter time constant for I signal
Input
I Input Minimum Current
Frequency Corresponding to I
Input Minimum Current
I Input Maximum Current
Frequency Corresponding to I
Input Maximum Current
Terminal I ( 0 ~ 20 mA )
I/O-09
I Maximum
current
01
20.0
20.0