Advertisement

Location Selection

DANGER
To avoid the possibility of fire, do not install the unit in an area where combustible gas may generate, flow, stagnate, or leak. Failure to do so will
cause serious bodily injury or death. Before beginning installation, read the safety summary at the beginning of this manual.
Select a location for installing the 4-Way Cassette Indoor Unit (IDU) that meets the following conditions:
• Where there is enough structural strength to bear the weight of the unit.
• Operating sound from the unit will not disturb occupants.
• Include enough space for service access.
• Include space for drainage to ensure condensate flows properly out of the unit when it is in cooling mode.
• Use a level indicator to ensure the unit is installed on a level plane.
• Use the provided pattern to determine the size of the ceiling opening and the hanging bolt locations required by the unit.
Do not install the unit where it will be subjected to direct thermal radiation from other heat sources.
Do not install the unit in an area where combustible gas may generate, flow, stagnate, or leak. There is the possibility of fire,
Do not install the unit in a location where acidic solution and spray (sulfur) are often used.
Do not use the unit in environments where oil, steam, or sulfuric gas are present.
Do not install additional ventilation products on the chassis of the unit.
Do not install the unit near high-frequency generator sources.

Required Clearances

Figure 6 shows required clearance distances around a typical installed ceiling cassette unit.
Ceiling Board
W
A
L
L

GENERAL INSTALLATION GUIDELINES

Figure 6: Required Clearances Around Installed Unit
Ceiling
4-way Ceiling Cassette
2x2 ft or 3x3 ft
19 -11/16
39 - 3/8
or more
or more
"A"
Any objects in room
(cabinets, furniture, etc.)
Floor
"A" =
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
No gap
required
Ceiling Board
19 -11/16
or more
Below 36 kBtu: at least 70 - 7/8; not more than 141 - 23/32
Over 36 kBtu: at least 70 - 7/8; not more than 165 - 11/32
11 -13/16
or less
Ceiling beam or
other obstruction
Unit: inch