TABLE OF CONTENTS Safety Precautions ....................3 I. Indoor Units Introduction......................8 Ceiling Cassette 4-way ..................10 Ceiling & Floor .......................37 Ceiling concealed Duct..................54 II. Outdoor Units Introduction......................76 MPS Variable Single A(AUUH-C, R410A) .............78 III. Troubleshooting Guide Self-diagnosis Function ..................102 Electronic Parts Troubleshooting Guide ..............103 IV.
Introduction • Model Number Nomenclature Indoor unit A T N H 1 8 6 E L F C Serial Number Functions A : Basic B : Low Ambient C : Plasma Filter E : Elevation Grille F : Elevation Grille + Plasma Filter H : Plasma Filter + Low Ambient L : Nano Plasma M : Nano Plasma + Elevation Grille...
Ceiling Cassette 4-way 1. Features & Benefits I Convenience • Auto elevation grille(Accessory) • Tele control(Accessory) • LCD wired remote control • Group control • Central control(Accessory) • Weekly progam I Cleanness • Plasma air purifying system • Hygienic and easy to clean filter I Easy Installation •...
Page 8
Ceiling Cassette 4-way Plasma Air Purifying System The PLASMA Air Purifying Function not only removes micro- scopic contaminants and dust, but also removes house mites, pollen, and pet fur helps to prevent allergic diseases like asthma. Dust electrode discharge Dust particles Ionizer Photo-Catalyst Coated Mesh +4.8KV discharge...
Ceiling Cassette 4-way Child Lock Function -It prevents the children or others from tampering with the control buttons. Unit can be controlled by the wireless remote controller. This can be easily set by pressing timer key & Min key simultaneously. After child lock is set, pressing any key will display CL on the LCD for 3 seconds and all the keys will be ineffective.
Ceiling Cassette 4-way Weekly Program - On/Off schedule of operation for a period of ONE week. No need to turn the unit On/OFF manually during working days. On/Off time is scheduled in micom of the wired remote control. Operation Time Table (Example) Setting Temp.
Ceiling Cassette 4-way 2. List of Functions Ceiling Cassette-4way Function ATNH-EL ATNH-FL ATNH-DL Air Discharge Outlet Airflow Direction control (left & right) Airflow Direction control (up & down) Auto Auto Auto Airflow Steps(Fan / Cool /Heat) 3/4/3 3/4/3 3/4/3 Auto Changeover Auto Elevation Grille Accessory Accessory...
Ceiling Cassette 4-way 5. Wiring Diagrams 5.1 Wiring Diagrams(Product) CONNECTOR NUMBER LOCATION CN-POWER AC POWER SUPPLY CN-MOTOR BLDC FAN MOTOR OUTPUT CN-D/PUMP DRAIN PUMP OUTPUT CN-DISP DISPLAY CN-FLOAT FLOAT SWITCH INPUT CN-PTC PTC HEATER INUT CN-REMO REMOTE CONTROL CN-GRILL GRILL CONTROL CN-CC CENTRAL CONTROL CN-PIPE2...
Ceiling Cassette 4-way 7. Operating Instructions I Name and Function of Remote Controller AUTO SWING OPERATION SET TEMP FAN SPEED SUB FUNCTION Room Temp Heat Pump Model AUTO Heater Preheat Defrost Humidify Filter Out door 1 2 3 4 Time ZONE Operation unit Program set...
Page 22
Ceiling Cassette 4-way I Wireless Remote Controller (optional) This air-conditioner is equipped with wired remote controller basically. But if you want to be available with wireless remote controller, you pay for it. 1. START/STOP BUTTON Operation starts when this button is pressed and stops when the button is pressed again.
Page 23
Ceiling Cassette 4-way I ELEVATION GRILL (REMOTE CONTROLLER_Accessory) • Main Components of Lift Grill Signal transmitter ➀ Lift grill front panel assembly ➁ Bolts for installation (4 EA, P/No. 3A00255K) ➂ Instruction manual Ascend ➃ Remote Controller for lift grill Descend Stop •...
Page 24
Ceiling Concealed Duct • How to Operate the Lift Grill • Always stop the air conditioner operation for safety before operating lift grill. • Take heed _ there is worry about dust fall etc. when suction grill descends. • In case when the set automatic stop distance goes wrong, check the set value of operation panel and con- firm if there is neither obstacle nor mankind.
Ceiling Cassette 4-way 8. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Anti-bacteria filter Intake Air Outlet...
Ceiling Cassette 4-way 8.2 Ceiling opening dimensions and hanging bolt location • The dimensions of the paper pattern for installation are the same as those of the ceiling opening dimensions. Ceiling Ceiling board Level gauge TE Model TF Model TD Model 600 (Ceiling opening) 790 (Ceiling opening) 875 (Ceiling opening)
Ceiling Cassette 4-way Ceiling Keep the length of the bolt Hanging bolt from the bracket to 40mm (W3/8 or M10) Flat washer for M10 Air Conditioner body (W3/8 or M10) (accessory) Ceiling board Ceiling board Spring washer (M10) Flat washer for M10 (accessory) Set screw of Paper pattern...
Ceiling Cassette 4-way 8.4 Installation of Decoration Panel Before installing the decoration panel, The decoration panel has its installation always remove the paper template. direction. 1. Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by amount 10mm in length.) The fixing screws (hexagon M5 screw) are included the indoor unit box.
Page 29
Ceiling Cassette 4-way 8.5 Installation of Decoration Panel(Elevation Grille) Before installing the decoration panel, The decoration panel has its installation always remove the paper template. direction. 1. Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by amount 10mm in length.) The fixing screws (hexagon M5 screw) are included unit box.
Page 30
Ceiling Concealed Duct • Don't lay any material upon suction grill. • Suction grill comprises 2 strands of wire. If any substance is placed on it then balance may be destroyed so that the substance would drop down and cause a breakage or damage. Also the matter may cause trouble owing to which the grill would not be correctly inserted at front panel.
Ceiling Cassette 4-way 8.5 Indoor Unit Drain Piping Upward Pipe clamp routing • Drain piping must have down-slope (1/50 to 1/100): be sure not allowed not to provide up-and-down slope to prevent reversal flow. Indoor unit • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit.
Ceiling Cassette 4-way 9. Accessories Standard Accessories Washer for Insulation for (Other) Clamp Clamp metal Name Drain hose hanging backet fitting Quantity 1 EA 1 EA 8 EA 8 EA 1 SET • Paper pattern for installation • Owner's manual •...
Ceiling & Floor 1. Features & Benefits I Flexible Installation I Low noise I 4-Way Airflow Direction Control (Automatic Vertical airflow & Manual Horizontal airflow) I LCD Wireless Remote Control Flexible Installation It can be installed on the floor or ceiling according to your need. <Ceiling Installation>...
Ceiling & Floor 2. List of Functions Ceiling & Floor (Convertible) Function AVNH-EL AVNH-BL AVNH-KL AVNH-LL Air Discharge Outlet Airflow Direction control (left & right) Manual Manual Manual Manual Airflow Direction control (up & down) Auto Auto Auto Auto Airflow Steps(Fan / Cool /Heat)
Ceiling & Floor 4. Dimensional Drawings AVNH-EL Signal receiver & Operation indicator Air discharge grille (Unit: mm) Note: 1. Pipe Specification(mm) Model Liquid Ø 6.35 Ø 9.52 Air suction grille <Ceiling Installation> <Floor Installation> More than 20Cm More than 20Cm...
Page 39
Ceiling & Floor AVNH-BL 1 2 0 0 Ø10 Stud Bolt hole (Rear Side) (Installation Plate) (Unit: mm) Note: 1. Pipe Specification(mm) Model Liquid 18k, 24k Ø 6.35 Ø 12.7 More than Ø 6.35 Ø 15.88 More than 20cm 20cm More than 20cm More than...
Page 40
Ceiling & Floor AVNH-KL/LL (unit: mm) Dimension Chassis VL Chassis 1750 1655 VK Chassis 1350 1255 More than Anchor nut 70cm Ceiling Washer Suspension bolts Suspension bolt More than 30cm More than 70cm Note 1. Pipe Specification(mm) Suspension bolts Model Liquid Spring washer...
Ceiling & Floor 7. Operating Instructions I Remote Control Operation The Remote Controller transmits the signals to the system. 1. START/STOP BUTTON Operation starts when this button is pressed and stops when Signal transmitter the button is pressed again. 2. OPERATION MODE SELECTION BUTTON Used to select the operation mode.
Ceiling & Floor 8. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Installation Parts Provided Installation Plate (VB, 2pcs) -1 Installation Plate (VE, 1pc)
Page 46
Ceiling & Floor 8.1 Selection of the best location More than 20cm • There should not be any heat source or steam near the More than 20cm unit. • There should not be any obstacles to the air circulation. More than eye-level •...
Page 47
Ceiling & Floor CAUTION 1. Install declination of the indoor unit is very important for the drain of the convertible type air conditioner. 2. Minimum thickness of the insulation for the connecting pipe shall be 7mm. 3. If the Installation Plates are fixed to horizontal line, the indoor unit after installing will be declined to the bottomside.
Page 48
Ceiling & Floor CAUTION After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have an individual power specially for the air conditioner. As for the method of wiring, be guided by the circuit diagram pasted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit.
Ceiling & Floor 9. Accessories Standard Accessories Washer for Insulation for (Other) Name Clamp metal Drain hose Clamp hanging backet fitting Quantity 1 EA 1 EA 8 EA 6 EA 1 set • Owner's manual • Installation manual Shape for gas pipe for liquid pipe Optional Accessories(For Unit) Item...
Ceiling Concealed Duct 1. Features & Benefits I Easy Installation • Compact & light design • (Linear E.S.P Control) • High head drain pump(700mm, Accessory) I Comfort & Reliability • Low noise design • 2-Thermistor control(Main body & Remote control) •...
Page 52
Ceiling Concealed Duct LG’s High Technology provide Easy and Low cost Design of Duct work Generally, when External Static Pressure increases air volume decreases. But by controlling the phase of motor while installing the product E.S.P. is controlled from 8~10 mmAq linearly. E.S.P. control provides required constant air volume irrespective of ESP change.
Ceiling Concealed Duct 2. List of Functions Ceiling Concealed Duct Function ABNH-HL ABNH-GL ABNH-RL Air Discharge Outlet Airflow Direction control (left & right) Airflow Direction control (up & down) Airflow Steps(Fan / Cool /Heat) 3/3/3 3/3/3 3/3/3 Auto Changeover Auto Operation Auto Restart Operation Auto Swing Central Control...
Ceiling Concealed Duct 7. E.S.P. Setting for (E.S.P. Control) provide required constant air volume irrespective of E.S.P. charge. (1) Open the rear cover of the wired remote-controller to set the mode. (2) Select one of three selectable modes as follows. I Without Zone System 1.
Page 60
Ceiling Concealed Duct How to Set E.S.P? Procedure of RPM change: Ex) External Static pressure is 4mmAq for Model Name "ABNH246HLAB". • To protect the unit, compressor is designed to be off during E.S.P. setting. Push the "On/Off" button. AUTO SWING OPERATION SET TEMP FAN SPEED SUB FUNCTION...
Page 61
Ceiling Concealed Duct Table 7-1 Static Pressure(mmAq) Step CMM(CFM) Model Name Setting Value High 16.5(583) ABNH186HLAC 14.5(512) 13(459) High 18(636) ABNH246HLAC 16.5(583) 14(494) High 26.5(936) ABNH306GLAC 23(812) 20(706) High 32(1130) ABNH366GLAC 29(1024) 26.5(936) High 40(1412) ABNH486RLAC 35(1235) 30(1059) High 50(1766) ABNH606RLAC 45(1589) 40(1423)
Page 62
Ceiling Concealed Duct Table 7-2 Static Pressure(mmAq) Setting Model Name Step Value CMM(CFM) High 22(777) 21(742) 19.8(669) 18.3(646) 16.5(583) ABNH186HLAC 18.5(653) 17.8(629) 17.1(604) 16.2(572) 14.5(512) 16.1(569) 15.6(551) 15.1(533) 14.2(501) 13(459) High 24(848) 22.5(795) 20.8(735) 19(671) 18(636) ABNH246HLAC 21.3(752) 19.9(703) 18.7(660) 17.2(607) 16.5(583) 17(600)
Ceiling Concealed Duct 8. Operating Instructions I Name and Function of Remote Controller AUTO SWING OPERATION SET TEMP FAN SPEED SUB FUNCTION Room Temp AUTO Heater Preheat Defrost Humidify Filter Out door Time 1 2 3 4 ZONE Timer Operation unit Program set Set no.
Page 64
Ceiling Concealed Duct I Optional Function • Wireless Remote Controller This air-conditioner is equipped with wired remote controller basically. But if you want to have the wireless remote controller, you pay for it. 1. FAN Operation Button Signal transmitter Used to circulate room air without cooling or heat- Transmits the signals to the signal receptor.
Ceiling Concealed Duct 9. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Air outlet vents Air filters Air intake vents...
Page 66
Ceiling Concealed Duct 9.2 Ceiling dimension and hanging bolt location I Installation of Unit Install the unit above the ceiling correctly. CASE 1 POSITION OF SUSPENSION BOLT • Apply a joint-canvas between the unit and duct to absorb unnecessary vibration. •...
Page 67
Ceiling Concealed Duct • Select and mark the position for fixing bolts. • Insert the set anchor and washer onto the suspen- • Drill the hole for set anchor on the face of ceiling. sion bolts for locking the suspension bolts on the ceiling.
Ceiling Concealed Duct 9.4 Insulation THERMAL INSULATION All thermal insulation must comply with local requirement. INDOOR UNIT Union for liquid pipe Thermal insulator for refrigerant pipe (Local supply) Thermal insulator for Refrigerant pipe and thermal piping(Local supply) insulator(Local supply) Hose crip for thermal insulator (Local supply) Overlap with thermal Thermal insulator for refrigerant pipe...
Page 69
Ceiling Concealed Duct CAUTION 1. Decline Installation of indoor unit is very important for the drain of the duct type air conditioner. 2. Minimum thickness of the insulation for the connecting pipe should be 5mm. Front of view • The unit must be or declined to wards drain hose while installation. Ceiling Drainage hole Drainage hole...
Ceiling Concealed Duct 10. Accessories Standard Accessories Screws for Insulation for Clamp (Other) Name Clamp metal Drain hose duct flanges fitting Quantity 1 EA 1 EA 1 set 6 EA 1 set • Owner's manual • Installation manual • Washers(8 pcs.) Shape for gas pipe for liquid pipe...
1 Compressor AUUH608C • Indoor Unit Matching LG’s system consist of one outdoor unit which can match with three different indoor units as individ- ual system. The indoor units are ceiling cassette, ceiling concealed duct and ceiling & floor types.
Page 73
Introduction MPS Variable SINGLE A • Model Number Nomenclature A U U H 1 8 6 C Serial Number Electric Standard (Phase, Volts, Freq) 6:1Ø,220V~240V,50Hz 8:3Ø,380V~415V,50Hz Nominal Cooling Capacity in Btu/h 60 : 60,000 Btu/h 12 : 12,000 Btu/h 18 : 18,000 Btu/h 24 : 24,000 Btu/h 30 : 30,000 Btu/h 36 : 36,000 Btu/h...
MPS Variable SINGLE A 1. Features & Benefits MPS(Multi Power System) Variable Control : (Except: AUUH126B/186B/246B/608B) Big Energy Saving with MPS Variable Control • Basic Principle of MPS Variable Control MPS control provides comfortable and convenient environment as there are two compressors with 60&40% load sharing with on compressor of small capacity always working to maintain the set temperature conditions &...
It can prevent frosting of evaporator and keep cooling operation on. 138%~133% Heating Capacity Improved 124% • Using MPS technology, LG's air conditioning sys- 120%~115% tem achieved world's best wide range of opera- 112% 120% tion which is from 12%~120% in cooling mode...
MPS Variable SINGLE A 2. Specifications Nominal Capacity and Nominal Input For combination indoor units + outdoor units : Indoor Units ATNH126ELFC ATNH186ELFC ATNH246FLFC ATNH306FLFC Outdoor Units AUUH126C AUUH186C AUUH246C AUUH306C Nominal Capacity Cooling Btu/h 12,000 18,000 24,000 30,000 3,517 5,275 7,033 8,793...
Page 78
MPS Variable SINGLE A Nominal Capacity and Nominal Input For combination indoor units + outdoor units : Indoor Units ATNH366DLFC ATNH486DLFC ATNH606DLFC Outdoor Units AUUH368C AUUH488C AUUH608C Nominal Capacity Cooling Btu/h 36,000 48,000 56,000 10,552 14,069 16,414 Heating Btu/h 39,600 52,800 61,600 11,607...
Page 79
MPS Variable SINGLE A Technical Specification Outdoor Units AUUH126C AUUH186C AUUH246C AUUH306C Running Current Cooling/Heating 7.5/7.0 8.4/9.2 11.0/12.0 20.0/20.0 Starting Current Cooling/Heating Power Supply Ø,V,Hz 1,220~240,50 1,220~240,50 1,220~240,50 1,220~240,50 Power Factor Compressor Type Rotary Rotary Rotary Rotary (Constant) Model GK151PAC 5KS225DAF21 GP290PAC 5KS225DKSM...
Page 80
MPS Variable SINGLE A Technical Specification Outdoor Units AUUH368C AUUH488C AUUH608C Running Current Cooling/Heating 7.8/6.6 11.5/11.0 32.5/31.5 Starting Current Cooling/Heating Power Supply Ø,V,Hz 3,380~415,50 3,380~415,50 3,380~415,50 Power Factor Compressor Type Rotary Rotary SCROLL (Constant) Model 5KS225PAA21 GPT330Y AR073YA Quantity Motor Input 2,065 2,550 6,473...
MPS Variable SINGLE A 3. Dimensional Drawings AUUH126C Gas side (3-way valve) Liquid side (2-way valve) MODEL AUUH126C unit Service Manual 85...
Page 82
MPS Variable SINGLE A AUUH186C/AUUH246C/AUUH306C Air discharge grille Model AUUH186C AUUH246C/306C Dimensions 74.5 74.5 Ø6.35 Ø6.35 Ø12.7 24k : Ø12.7, 30k : Ø15.88 86 Universal System Air Conditioner...
Page 83
MPS Variable SINGLE A AUUH368C 4-holes for anchor bolts (Unit: mm) Number Name Descripition Liquid side service valve(mm) Ø6.35 Gas side service valve(mm) Ø15.88 Air discharge grill Control Cover Service Manual 87...
Page 84
MPS Variable SINGLE A AUUH488C/AUUH608C 4-hole for anchor bolts Control cover Liquid side 3-way valve Gas side 3-way valve Model AUUH488C/AUUF608C Dimensions 1,165 1,135 Ø9.52 Ø19.05 88 Universal System Air Conditioner...
MPS Variable SINGLE A 7. Operation Range Item Range Inlet air temperature (Cooling) 46(114.8) Standard operation -10(14) 14(57.2) 24(75.2) Indoor air temperature °C W.B.(°F) Inlet air temperature (Heating) 15.5(59.9) Standard operation -10(14) 14(57.2) 28(82.4) Indoor air temperature °C D.B.(°F) Power source voltage Rating ±10% Voltage at starting Min.
MPS Variable SINGLE A 8. Installation 8.1 Selection of the best location • If a roof is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted. • Do not place animals and plants in the path of the warm air. •...
Page 95
MPS Variable SINGLE A 8.3 Piping length and the elevation Pipe Size Length Elevation *Additional Capacity (Diameter:Ø) refrigerant(g/m) Liquid Standard Max. Standard Max. 3/8" 1/4" 12k Btu/h (9.52mm) (6.35mm) 1/2" 1/4" 18k Btu/h (12.7mm) (6.35mm) 1/2" 1/4" 24k Btu/h (12.7mm) (6.35mm) 5/8"...
MPS Variable SINGLE A 8.5 Wiring Connection 1. All wiring must comply with LOCAL REGULATIONS. 2. Select a power source that is capable of supplying the current as required by the air conditioner. 3. Feed the power source to the unit via a distribution switch board designed for this purpose. 4.
Troubleshooting Guide III. Troubleshooting Guide Self-diagnosis Function ................102 Electronic Parts Troubleshooting Guide ............103 Service Manual 101...
Troubleshooting Guide Self-diagnosis Function I Error Indicator The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble. If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed. After error occurrence, if error is released, error LED is also released simultaneously. Having or not of error code is different from Model.
Electronic Parts Troubleshooting Guide Troubleshooting Guide Electronic Parts Troubleshooting Guide 1. The Outdoor Unit does not operate at all Does the Operating LED of indoor unit blink Refer to the self-diagnosis function. when Operation’s ON? Is the Connection between CN-Power of indoor Check the connecting state of connector unit and terminal block? Indoor...
Electronic Control Device Electronic Parts Troubleshooting Guide 2. The product is not operate with the remote controller. Turn on Main Power While the compressor has been stopped, the compressor does not operate owing to the delaying function for 3 minutes after stopped. When the compressor stopped Indoor Fan is driven by a low speed.
Page 101
Electronic Parts Troubleshooting Guide Electronic Control Device 3. When cooling does not operate Turn on Main Power Operate "Cooling Mode( )" by setting the desired temperature of the remote controller is less than one of the indoor temperature by 1°C at least. When in Air Circulation Mode, Compressor/Outdoor Fan is stopped.
Electronic Control Device Electronic Parts Troubleshooting Guide 4. When Heating does not operate Turn ON Main Power Operate “Heating Mode( )” by setting the desired temperature of the remote control is higher than one of the indoor temperature by 2°C at least.
Electronic Parts Troubleshooting Guide Electronic Control Device 5. When indoor Fan does not operate Turn off Main power Check the connection of CN-FAN or CN-MOTOR Check the Fan Motor Check the Fuse(AC250V/T2A) Check the related circuit of indoor Fan Motor. •...
Electronic Control Device Electronic Parts Troubleshooting Guide 6. When Vertical Louver does not operate • Confirm that the Vertical Louver is normally geared with the shaft of Stepping Motor. • If the regular torque is detected when rotating the Vertical Louver with hands Normal •...
Electronic Control Device IV. Electronic Control Device Ceiling Cacsette Type...................110 Ceiling Duct Type..................111 Celing & Floor ....................113 Service Manual 109...
Ceiling Cassette Type Ceiling Cassette Type The function of main control I Auto Swing Control • This function is to swing the louver up and down automatically. I Soft-Dry Operation • The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of already being set to the best speed for Dry Operation by microcontroller control.
Ceiling Cassette Type I Heating Mode Operation The unit will operate according to the setting by the remote controller and the operation diagram is shown as following. Indoor unit 35°C Heat-Exchanger temperature 32°C 29°C 21°C 17°C Intake Air Temperature 3min Low fan during 10sec Setting Temperature +4°C(Unit Sensing)
Ceiling Duct Type Ceiling Duct Type The function of main control I Soft-Dry Operation • The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of already being set to the best speed for Dry Operation by microcontroller control. I Cooling Mode Operation •...
Page 119
Ceiling Duct Type I Heating Mode Operation The unit will operate according to the setting by the remote controller and the operation diagram is shown as following. Indoor unit 40°C Heat-Exchanger temperature 33°C 30°C 27°C 20°C Intake Air Temperature 3min Low fan during 10sec Setting Temperature +4°C(Unit Sensing)
Page 120
Ceiling Duct Type I Hot-Start Control • The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 27°C. • The operation diagram is as following. Indoor unit Heat-Exchanger temperature 33°C 27°C 20°C 1min 1min Compressor Outdoor fan Setting fan Setting fan Indoor fan...
Ceiling & Floor Ceiling & Floor The function of main control I Soft-Dry Operation • The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of already being set to the best speed for Dry Operation by microcontroller control. I Cooling Mode Operation •...
Page 122
Ceiling & Floor I Heating Mode Operation The unit will operate according to the setting by the remote controller and the operation diagram is shown as following. Indoor unit 35°C Heat-Exchanger temperature 32°C 29°C 21°C 17°C Intake Air Temperature 3min Setting Temperature Low fan during 10sec +4°C(Unit Sensing)
Page 123
Ceiling & Floor I Hot-Start Control • The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 21°C. • The operation diagram is as following. Indoor unit Heat-Exchanger temperature 32°C 21°C 17°C 1min Compressor Outdoor fan Setting fan Setting fan Indoor fan spped...
Outdoor Units Outdoor Units 1.Basic control 1.1 Normal operation Cooling mode Heating mode Stop state On/Off (1 Comp.) On/Off (1 Comp.) Stop Compressor Step Control (2 Comp.) Step Control (2 Comp.) Phase control Phase control After 30sec, Off Target Suction super heat and Target Suction super heat and After 60sec, Full Opne Discharge Temp.
Page 125
Outdoor Units (2) Operation field for Temp. Cooling Outdoor Temp. 46°C 45°C 1 Step Down 44°C 43°C Hysterisis Standard Step 22°C 23°C 21°C 24°C Indoor Temp. Heating Outdoor Temp. 18°C 17°C 1°C 1 Step Down 0°C Hysterisis Standard Step Indoor Temp. 23°C 24°C 27°C...
Outdoor Units 1.3 EEV Control 1) The base(the first stage) open_degree’s establishment The base open_degree is established [the standard open_degree classified by indoor_Type and capacity ] that corrected to the indoor/outdoor Temp. 2) Starting Control (LEV target open_degree arrival process after starting Comp) (1) LEV is arrived the previous decided open_degree within 30 seconds after starting COMP.
Outdoor Units (4) Compressor Discharge-Temp. Control After 1 min. of normal control, if it is satisfied with fomula below, it starts to control of Comp. Discharge Temp. Cooling mode : The present degree of superheat ≤ 3 (Option) Heating mode : The target degree of superheat < 0 , The present degree of superheat ≤ 0 (Option) The present degree of superheat ≥...
Page 128
Outdoor Units 1.5 Reversing Valve Control 1. The first situation of reversing valve maintains off(cooling) (Before that The power turns on the set of out- door_unit and indoor_unit ) 2. While the Cooling and Defrosting Process the Reversing valve control is OFF and during the Heating Process the Reversing valve control is ON 3.
Outdoor Units 2. Special control 2.1 Defrost control : In case the temperature of the outdoor unit heat exchanger falls continuously this function will prevent heat exchanger from freezing. 2.1.1 Defrost PROCESS Starting conditions 1) Only Operates in the heating mode. 2) The defrost timer (The first time : outdoor unit is turned on ,the minimum for defrost operation to start is over 45~120 minutes.
Page 130
Outdoor Units 2.2 Low ambient control 2.2.1 The outline of Low ambient control. : The control device makes [the outdoor_unit] operate the Cooling mode in low-temperature condition with- out overloading the comp. If the Temp. of outdoor_unit goes down, The Evaporator will start freezing and the liquid refrigerant will flow inside the Compressor.
Page 131
Outdoor Units 2.3 Oil control : COMP OIL Equalizing Control ( Only 2 COMPRESSOR Model) : To equalize the oil level in each Compressors. 1) COMP OIL Equalizing Logic 1. When the running time of solo operation of the specific COMP is over 1 hour. The other compressor will be operated at least for 30 seconds 2.
Outdoor Units 3. Protection control 3.1 Discharge Temperature control Discharge pipe Temperature COMP OFF 105°C LEV OPEN (20PULSE/MIN ) 90°C LEV OPEN (10PULSE/MIN ) 70°C COMP ON 3.1.1 The outline of Discharge Temperature control This function prevents the damage of COMP according to EEV Comp On/Off control. - The EEV Comp On/Off control is predicted the Temp.
Page 133
Outdoor Units 3.2 Outdoor pipe Temperature control - Outdoor pipe Temperature(condensation Temp.) is over 58 (or 60)°C according to overlord in Cooling mode, the COMP will be switched is OFF. - Error code (CH61) will be generated if this situation occurs 5times (or 10times) in 40 minutes (or 1 hour). - The Error code will be cleared if this situation occurs lower than 4times(or 9times) in 40 minutes (or 1 hour).
Page 134
Outdoor Units 138 Universal System Air Conditioner...
Page 135
VI. Exploded View & Replacement Parts List Indoor Unit ....................140 Outdoor Unit ....................159 Panel Assembly, Front .................173 Service Manual 139...
Exploded View & Replacement Parts List Parts List Part No. LOCATION DESCRIPTION SVC CODE ABNH186HLAC ABNH246HLAC 336610-1 HOUSING(MECH),WRAPPER 3660A20017A 3660A20017A 336610-2 HOUSING(MECH),WRAPPER 3660A20018A 3660A20018A 346810 MOTOR ASSEMBLY, AC 4681A10013C 4681A10013C 359012-1 FAN ASSEMBLY,BLOWER 5901A10026A 5901A10026A 359012-2 FAN ASSEMBLY,BLOWER 5901A10028B 5901A10028B W0CZZ CAPACITOR, FILM, BOX 2A00986D...
Page 148
Exploded View & Replacement Parts List Part No. LOCATION DESCRIPTION SVC CODE ABNH306GLAC ABNH366GLAC 336610-1 HOUSING(MECH),WRAPPER 3660A20019A 3660A20019A 336610-2 HOUSING(MECH),WRAPPER 3660A20020A 3660A20020A 346810 MOTOR ASSEMBLY, AC 4681A10013J 4681A10013A 359012-1 FAN ASSEMBLY,BLOWER 5901A10026A 5901A10026A 359012-2 FAN ASSEMBLY,BLOWER 5901A10026A 5901A10026A W0CZZ CAPACITOR, FILM, BOX 2A00986D 2A00986D 354210...
Page 149
Exploded View & Replacement Parts List Part No. LOCATION DESCRIPTION SVC CODE ABNH486RLAC ABNH606RLAC 336610-1 HOUSING(MECH),WRAPPER 3660A20044A 3660A20044A 336610-2 HOUSING(MECH),WRAPPER 3660A20045A 3660A20045A 346810 MOTOR ASSEMBLY, AC 4681A10032A 4681A10032A 359012-1 FAN ASSEMBLY,BLOWER 5901A10051A 5901A10051A 359012-2 FAN ASSEMBLY,BLOWER 5901A10051A 5901A10051A W0CZZ CAPACITOR, FILM, BOX 0CZZA20001B 0CZZA20001B 354210...