External Static Pressure & Air Flow
How to Set E.S.P?
Procedure of RPM change:
Ex) External Static pressure is 6mmAq for Model Name "ABNH368GLAA"
• To protect the unit, compressor is designed to be off during E.S.P. setting.
Push the "On/Off" button.
1
The unit will start.
Push the "Timer" and "Wind" button simultaneously for more then 3 seconds.
2
Timer
Push the "Up" of "Down" button for E.S.P adjustment.
3
And, adjust the number which you want.(In this example, the number is "220". Refer to the
table 15-2 on the next page.)
Note: The range of selection is from 1~254. Since, the display is two Digit only.
If the range selection is above 100 then the third digit will appear in the screen as shown.
Shift the fan speed mode by pressing the fan speed button.
4
And then, Adjust numbers of next steps by repeating the stage 3.
(In this example, the numbers are "245" and "253" respectively.
Push the "Timer" and "Wind" button simultaneously for more than 3 seconds.
5
Then, Wind Data is memorized by the EEPROM of the main PCB.
Timer
58 Universal System Air Conditioner
AUTO SWING
OPERATION
SET TEMP
FAN SPEED SUB FUNCTION
Room Temp
HI
MED
LO
Time
ZONE
Timer
Operation unit
Program set
On
Off
Set no. Time
01
03
05
07
09
11
13
15
AUTO SWING
OPERATION
SET TEMP
FAN SPEED
Room Temp
HI
MED
LO
Time
ZONE
Timer
Operation unit
Program set
On
Off
01
03
05
07
09
11
13
15
Set no. Time
AUTO SWING
OPERATION
SET TEMP
FAN SPEED
Room Temp
HI
MED
LO
Time
ZONE
Timer
Operation unit
Program set
On
Off
Set no. Time
01
03
05
07
09
11
13
15
AUTO SWING
OPERATION
SET TEMP
FAN SPEED SUB FUNCTION
Room Temp
HI
MED
LO
Time
ZONE
Timer
Operation unit
Program set
On
Off
Set no. Time
01
03
05
07
09
11
13
15
AUTO
Heater
Preheat
JET
Defrost
Humidify
Filter
Out door
1 2 3 4
17
19
21
23
SUB FUNCTION
AUTO
Heater
Preheat
JET
Defrost
Humidify
Filter
Out door
1 2 3 4
17
19
21
23
SUB FUNCTION
AUTO
Heater
Preheat
JET
Defrost
Humidify
Filter
Out door
1
2
3 4
17
19
21
23
AUTO
Heater
Preheat
JET
Defrost
Humidify
Filter
Out door
1 2 3 4
17
19
21
23