Electrical Data
Table 4: Electrical Data.
Nominal
Unit Model No.
Tons
Low Static
3/4
LUU097HV
1
LUU127HV
1.5
LUU189HV
High Static
2
LUU249HV
3
LUU369HV
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
RLA = Rated Load Amps.
Voltage
Hertz Voltage
Range
(Min. to Max.)
60
208 - 230
187 - 253
60
208 - 230
187 - 253
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows:
(Largest motor FLA x 2.25) + (Sum of other motor FLA) rounded down
to the nearest standard fuse size.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
ELECTRICAL DATA
Compressor
MCA
MOP
Quantity
11.9
15
12.3
1
20
30
20
30
1
32
40
Condenser Fan Motor(s)
Compressor
Motor RLA
Condenser
Condenser Fan
(Cooling)
Fan Quantity.
9.0
1
13.5
13.5
1
22
2
Motor FLA
0.25
1.6
1.6
1.6 x 2
DUCTED | 13