Electrical Data
Table 4: Electrical Data.
Nominal
Unit Model
Hertz Voltage
Tons
No.
Low Static
1.5
LUU180HHV
60
High Static
2
LUU240HHV
3
LUU360HHV
60
3.5
LUU420HHV
4
LUU480HHV
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
RLA = Rated Load Amps.
Voltage
Range
MCA MOP
(Min. to Max.)
208 - 230
187 - 253
22
22
32
208 - 230
187 - 253
32
32
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows:
(Largest motor FLA x 2.25) + (Sum of other motor FLA) rounded down
to the nearest standard fuse size.
©
ELECTRICAL DATA
Compressor
Compressor
Motor RLA
Quantity
(Cooling)
30
1
14.5
30
14.5
40
22
1
40
22
40
22
Condenser Fan Motor(s)
Locked
Rotor
Condenser
Condenser Fan
Amps
Fan Quantity.
Motor FLA
23
1
23
1
33
2
1.6 x 2
33
2
1.6 x 2
33
2
1.6 x 2
DUCTED | 13
1.6
1.6