Chapter 8. PROGRAMMING
8.2.3 A Program when Loading the RTD Input Module onto the Remote I/O Station
1) System Configuration
GM3-
GM3-
G7L-
PA1A
CPUA
FUEA
2) Initial Settings
(1) Specifying used channel : channel 0
(2) Specifying the type of the RTD : Pt 100
3) Descriptions of the Program
(1) P0010 turns on if the temperature value detected at channel 0 is more than or equal to –10°C.
(2) P0011 turns on if the temperature value detected at channel 0 is less than –10°C and more than or
equal to –20°C.
(3) P0012 turns on if the temperature value detected at channel 0 is less than –20°C.