Chapter 7. DEDICATED INSTRUCTIONS FOR SPECIAL MODULES
7.1.2 Write to Buffer Memory ⋅ ⋅ ⋅ PUT, PUTP
<Format>
Format
n1
The number of the slot where the specific module mounted
First address of the specific module buffer memory to which the
n2
data will be written..
First address of the device where the data to be written has been
S
stored, or an integer
n3
Word number of data to be written .
PUT: always executed if the execution condition turns On. .(
PUTP : executed if the execution condition is triggered. . (
Example 1) In this example, the RTD input module is loaded on the slot 6 in the base unit
and the data of CPU module addresses D50 and D51 will be written to the buffer memory
addresses 3 and 4.
(address)
D48
D49
D50
D51
D52
<PUT>
execution condition
execution condition
<PUTP>
execution condition
for PUT
Descriptions
<The difference between PUT and PUTP>
CPU module D area
Data 1
Data 2
PUT 00006 00003 D0050 00002
for PUT
for PUTP
M0000
PUTP 00006 00003 D0050 00002
PUT
n1
n2
S
Specifying type of RTD of Ch 2
Specifying type of RTD of Ch 3
D
M0000
7 - 2
n3
Available Data Type
Integer
Integer
M,P,K,L,T,C,D,#D
Integer
)
)
RTD input module
buffer memory
(address)
1
2
3
4
5