ELECTRICAL DATA

Electrical data for 208–230V Models
Table 10: 208-230V, 60Hz, 3-Phase Systems
Nom.
System Model No.
Tons
6
ARWM072BAS5
8
ARWM096BAS5
10
ARWM121BAS5
12
ARWM144BAS5
14
ARWM168BAS5
16
ARWM192BAS5
18
ARWM216BAS5
20
ARWM240BAS5
22
ARWM264BAS5
24
ARWM288BAS5
30
ARWM360BAS5
36
ARWM432BAS5
For component model numbers, see the specification tables.
For 208−230V systems, acceptable voltage range is 187−253V.
Maximum allowable voltage imbalance is 2%.
22 | WSU PRODUCT DATA
Compressor
Motor RLA
Comp.
Qty.
Frame 1
Frame 2
1
11.1
-
1
15.5
-
1
22.2
-
1
26.2
-
2
15.5
11.1
2
15.5
15.5
2
22.2
15.5
2
22.2
22.2
2
26.2
22.2
2
26.2
26.2
3
22.2
22.2
3
26.2
26.2
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG " is a registered trademark of LG Corp.
MCA
Frame 1
Frame 2
Frame 3
-
13.8
-
-
19.4
-
-
27.7
-
-
32.7
-
-
19.4
13.8
-
19.4
19.4
-
27.7
19.4
-
27.7
27.7
-
32.7
27.7
-
32.7
32.7
22.2
27.7
27.7
26.2
32.7
32.7
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOCP) is calculated as follows: (Largest motor RLA x 2.25) + (Sum of
other motor RLA) rounded down to the nearest standard fuse size.
SCCR rating: 56 kA RMS symmetrical 208V maximum / 62 kA RMS symmetrical 230V maximum
MOCP
Frame 3 Frame 1 Frame 2 Frame 3
-
20
-
-
30
-
-
45
-
-
50
-
-
30
20
-
30
30
-
45
30
-
45
45
-
50
45
-
50
50
27.7
45
45
32.7
50
50
-
-
-
-
-
-
-
-
-
-
45
50

Hide quick links: