Closing shutoff valve
1
Remove the cap and turn the valve clockwise with the hexagon wrench.
2
Securely tighten the valve until the shaft contacts the main body seal.
3
Make sure to tighten the cap securely.
* For the tightening torque, refer to the table on the below.
Tightening torque
Shutoff
valve size
Shaft(valve body)
Ø6.35
6±0.6
Ø9.52
wrench 4mm
Ø12.7
9±0.9
Ø15.88
15±1.5
wrench 6mm
Ø22.2
±3
30
wrench 10mm
Ø25.4
Insulation of shutoff valve
1
Use the heat insulation material for the refrigerant piping which has an excellent heat-resis-
tance (over 120°C).
2
Precautions in high humidity circumstance:
This air conditioner has been tested according to the "ISO Conditions with Mist" and con-
firmed that there is not any default. However, if it is operated for a long time in high humid at-
mosphere (dew point temperature: more than 23°C), water drops are liable to fall. In this
case, add heat insulation material according to the following procedure:
- Heat insulation material to be prepared... EPDM (Ethylene Propylene Diene Methylene)-over
120°C the heat-resistance temperature.
- Add the insulation over 10mm thickness at high humidity environment.
Tightening torque N·m(Turn clockwise to close)
Cap(Valve lid) Service port
29.4±2.9
Hexagonal
Hexagonal
53.9±5.8
Hexagonal
Indoor unit
Flare nut Gas line piping attached to unit
16±2
38±4
55±6
12.7±2
75±7
-
Fastening band
(accessory)
Refrigerant piping
Thermal insulator
(accessory)
INSTALLATION
25
-
25±3