hit counter script

Branch Pipe Fitting - LG Multi V ACRUN040LSS0 Installation Manual

Table of Contents

Advertisement

PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
44

Branch pipe Fitting

Y branch
A
• Ensure that the branch pipes are attached horizontally or vertically. (see the diagram below.)
A
• There is no limitation on the joint mounting configuration.
• If the diameter of the refrigerant piping selected by the procedures described is different from
the size of the joint, the connecting section should be cut with a pipe cutter.
• Branch pipe should be insulated with the insulator in each kit.
Insulator
(included with kit)
Header
B
Horizontal
plane
Viewed from point A
in direction of arrow
Liquid and gas
pipe joints
Ⓐ To Outdoor Unit Ⓑ To Indoor Unit
A
• The indoor unit having larger capacity must be
• If the diameter of the refrigerant piping selected
B
ⓒ Pipe cutter
C
• When the number of pipes to be connected
Ⓐ To Branch Piping or Indoor Unit
Ⓑ To Outdoor Unit
Within +/- 10°
Tape
(field supply)
Insulator for
field piping
installed closer to Ⓐ than smaller one.
by the procedures described is different from the
size of the joint, the connecting section should
be cut with a pipe cutter.
is smaller than the number of header
branches, install a cap to the unconnected
branches.
Facing
Facing
downwards
upwards
Within ±3° Within ±3°

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Uploaded: cache9/manual/2443312/Lg-Multi-V-Acrun040lss0.html%3Fpage%3D44.gz