Communications Cable Specifications Between Multiple Indoor Units Operat-
ing as a Group (Group Control)
If any indoor units were specified to operate in unison:
• Before running cable, decide which indoor unit will be the "Mas-
ter." The other indoor units in that group will be designated as
"Slave(s)." The zone controller will be connected to the "Master."
• Set the pertinent DIP switch at each indoor unit to identify the
Master and Slave(s).
• Use a daisy chain configuration and connect all of the group's
indoor units together starting at the "Master" unit.
NEVER splice, cut, or extend LG provided cable with field
provided cable. Always include enough cable to cover distance
between all components.
• Perform group control settings and connect the group control
wiring after the system auto address and auto pipe procedures
have been completed.
For indoor units with hardwired connections SIG - 12V - GND
(Comm.) terminals:
• From the controller to the master indoor unit, use 22 AWG,
3-conductor, twisted, stranded, unshielded. All wiring must com-
ply with all applicable local and national codes.
• From the master indoor unit to the slave indoor unit(s), daisy
chain using 22 AWG, 3-conductor, twisted, stranded, unshielded
(
Do not attach wire to 12VDC terminal to the slave indoor
units). All wiring must comply with all applicable local and
national codes.
For indoor units with CN-REMO connections:
Use Group Control Kit (sold separately) containing extension and
Y-splitter cables. Use one (1) group control cable kit for each indoor
unit in the group except for the last indoor unit.
• Cable connected to zone controller is the factory default connection.
• Indoor unit connections depend on indoor unit type.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Communications Cable Specifications
Figure 46: Example of Indoor Unit Group to Zone Controller
Connections (Sig-12V-GND [Comm.] Terminal).
Master Indoor Unit
Indoor Unit
Signal
12VDC Comm.
Signal
4
5
6
Signal
12VDC Comm.
Figure 47: Example of Indoor Unit Group to Zone Controller
Connections (CN-REMO).
Indoor Unit
Master Indoor Unit
CN-REMO
CN-REMO
LG
Supplied
LG Supplied Group Control Kit (PZCWRCG3)
WIRING
Indoor Unit
Signal
12VDC Comm.
12VDC Comm.
Indoor Unit
CN-REMO