hit counter script

LG MULTI V ARNU073M1A4 Installation Manual page 43

Ducted indoor units
Hide thumbs Also See for MULTI V ARNU073M1A4:
Table of Contents

Advertisement

A properly installed pipe system will have sufficient support so that pipes will not sag during the life of the system. As necessary, place supports
closer for segments where potential sagging could occur. Maximum spacing of pipe supports must meet local codes.
Figure 28: Pipe Support at Indoor Unit.
Refrigerant Pipe Connections
Indoor units come with flare type connections. It is the installer's option to use the flare fittings provided or braze the indoor unit to the
refrigerant piping system. The vertical air handling unit (VAHU) comes with brazed connections only.
Flare Fittings
• All unit flare fittings are 45° and rate for high-pressure R410A refrigerant.
• Properly form all flare fittings using best practices.
• Place a drop of PVE oil on the outside of the flare fitting before
tightening.
Note:
Do not use any other type of oil (including traditional POE refrig-
eration oil) as a lubricant. Failure to follow this procedure may lead to
restrictions in the refrigeration components.
Do not over-tighten flare nuts. Excessive tightening will cause
fittings to crack.
Note:
Multi V refrigeration system components contain very small capillary
tubes, small orifices, electronic expansion valves, oil separators, and
heat exchangers that can easily become blocked.
Insulate Refrigerant Pipes
Sufficiently insulate all cold surfaces to prevent moisture forming. All
pipes must be insulated and each pipe must be separately wrapped.
Refer to Figure 30 and Figure 31. Use field-provided one-half (1/2)
inch thick (or thicker) closed-cell insulation. The thickness may need
to be increased based on ambient conditions and local codes.
Wrap all refrigerant piping including field-provided isolation ball valves
and flexible pipe connection kits provided by LG. Glue all insulation
joints with no air gaps between insulation segments, and between
insulation segments and the unit case. Ensure insulation material fits
snugly against the refrigeration pipe with no air space between the
pipe surface and the surrounding insulation.
Protect insulation inside hangers and supports with a second insula-
tion layer. Ensure insulation on all pipe passing through pipe hangers,
inside conduit, and/or sleeves is not compressed.
B
A
A + B ~ 12" – 19"
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
REFRIGERANT PIPING
Figure 29: Typical Pipe Support Location—Change in Pipe Direction.
~ 12" – 19"
Figure 30: Typical Refrigerant Line Flare Fitting Insulation Detail
Insulation for Indoor Unit Port
(Field Supplied)
Insulation Clip (Field Supplied)
No Clearance
Figure 31: No Air Gap in Pipe Insulation to Indoor Unit Frame.
Max. 12"
Insulation for Refrigerant
Piping (Field Supplied)
Overlap Insulation Where the
Port and the Piping Meet
43

Advertisement

Table of Contents
loading

Table of Contents

Uploaded: cache9/manual/1933728/Lg-Multi-V-Arnu073m1a4.html%3Fpage%3D43.gz