Plumbing materials and storage methods

Pipe must be able to obtain the specified thickness and should be used with low
impurities.
Also when handling storage, pipe must be careful to prevent a fracture, deformity
and wound.
Should not be mixed with contaminations such as dust, moisture.
Refrigerant piping on three principles
Drying
Should be no moisture
Items
- Significant hydrolysis of refrigerant
oil
Cause fail-
- Degradation of refrigerant oil
ure
- Poor insulation of the compressor
- Do not cold and warm
- Clogging of EEV, Capillary
- No moisture in the pipe
- Until the connection is completed,
the plumbing pipe entrance should
be strictly controlled.
- Stop plumbing at rainy day.
Countermea
- Pipe entrance should be taken
sure
side or bottom.
- When removal burr after cutting
pipe, pipe entrance should be
taken down.
- Pipe entrance should be fitted cap
when pass through the walls.
inside
Moisture
- Degradation of refrigerant oil
- Poor insulation of the compressor
- Do not cold and warm
- Clogging of EEV, Capillary
- No dust in the pipe.
- Until the connection is completed,
the plumbing pipe entrance should
be strictly controlled.
- Pipe entrance should be taken
side or bottom.
- When removal burr after cutting
pipe, pipe entrance should be
taken down.
- Pipe entrance should be fitted cap
when pass through the walls.
Cleanliness
No dust inside.
Dust
- Gas shortages
- Degradation of refrigerant oil
- Poor insulation of the compressor
- Do not cold and warm
- Airtightness test should be.
- Brazing operations to comply with
standards.
- Flare to comply with standards.
- Flange connections to comply with
standards.
Installation
Airtight
There is no refrigerant
leakage
Leakage
Installation Manual 13